Operating Instructions
2/2 A6V12232111_----_b A5W00134893C_AB 2022-01-18 Siemens Smart Infrastructure
17 Fan speed set
风速设定
0014 1 R/W 0x03 0x06 / 0x10 3 - 0 0: AUTO / 自动
1: Fan speed 1 / 风速 1
2: Fan speed 2 / 风速 2
3: Fan speed 3 / 风速 3
4: Fan speed 4 / 风速 4
5: Fan speed 5 / 风速 5
6: Fan speed 6 / 风速 6
7: Fan speed 7 / 风速 7
18 Indoor unit error code
室内单元错误代码
0015 1 R/W 0x03 0x06 / 0x10 3 - - 0: No error / 无错误
100...999: Error codes / 错误代码
19 Indoor unit error sign
室内单元错误信号
0016 1 R/W 0x03 0x06 / 0x10 3 - - 0: No error / 无错误
1: Error / 错误
20 P01 0030 1 R/W 0x03 0x06 / 0x10 4 - 1 0 = AUTO/HEAT/COOL/FAN/Dehumidification
1 = HEAT/COOL/FAN/Dehumidification
2 = HEAT/COOL/FAN
3 = HEAT/COOL
4 = HEAT/FAN
5 = COOL/FAN/Dehumidification
6 = COOL/FAN
0 = 自动/制热/制冷/送风/除湿
1 = 制热/制冷/送风/除湿
2 = 制热/制冷/送风
3 = 制热/制冷
4 = 制热/送风
5 = 制冷/送风/除湿
6 = 制冷/送风
21 P02 0031 1 R/W 0x03 0x06 / 0x10 4 - 1 1 = ON – OFF /
开启
–
关闭
2 = ON – ECO – OFF /
开启
–
节能
–
关闭
22 P03 0032 1 R/W 0x03 0x06 / 0x10 4 - 1 0 = 0.5 K
1 = 1 K
23 P04 0033 1 R/W 0x03 0x06 / 0x10 4 - 0 0 = ℃ (Celsius) / (摄氏度)
1 = °F (Fahrenheit) / (华氏度)
24 P05 0034 1 R/W 0x03 0x06 / 0x10 4 x50 0 -5…5 K
25 P06 0035 1 R/W 0x03 0x06 / 0x10 4 - 0 0 = Room temperature / 室内温度
1 = Setpoint / 设定值
2 = BUS temperature / 总线温度
26 P08 0036 1 R/W 0x03 0x06 / 0x10 4 x50 21 ℃ 5…40 ℃
27 P09 0037 1 R/W 0x03 0x06 / 0x10 4 x50 5 ℃ 5℃…P10 (P10 = 40 ℃ max. / 最大)
28 P10 0038 1 R/W 0x03 0x06 / 0x10 4 x50 35 ℃ (P09 = 5 ℃ min. / 最小) P09…40 ℃
30 P14 0040 1 R/W 0x03 0x06 / 0x10 4 - 0 0 = Unlock
1 = Setpoint & fan buttons adjustment only
2 = Full lock
0 = 解锁
1 =仅温度设定值和风速可调
2 =全锁
34 P27 0044 1 R/W 0x03 0x06 / 0x10 4 - 0 0 = Previous operating mode /
前一运行模式
1 = OFF / 关闭
2 = ON (Normal mode) /
开启(标准模式)
35 P28 0045 1 R/W 0x03 0x06 / 0x10 4 - 1 0 = Disable / 禁用
1 = Enable / 启用
41 P53 0051 1 R/W 0x03 0x06 / 0x10 4 - 3 1 = 1-speed / 1 速
2 = 2-speed / 2 速
3 = 3-speed / 3 速
4 = 4-speed / 4 速
5 = 5-speed / 5 速
6 = 6-speed / 6 速
7 = 7-speed / 7 速
46 P71 0057 1 R/W 0x03 0x06 / 0x10 4 - 0 0 = Disable / 禁用
1 = Reload start / 开始重载
47 P81 0058 1 R/W 0x03 0x06 / 0x10 5 - 247 1…247
48 P82 0059 1 R/W 0x03 0x06 / 0x10 5 - 2 1 = 9600 bps
2 = 19200 bps
3 = 38400 bps
4 = 57600 bps
49 P83 0060 1 R/W 0x03 0x06 / 0x10 5 - 0 0 = 1/8/E/1
1 = 1/8/O/1
2 = 1/8/N/1
3 = 1/8/N/2
50 P98 0061 1 R/W 0x03 0x06 / 0x10 5 - 1 0 = Disable / 禁用
1 = Enable / 启用