Mounting Instructions

2/2 2022-03-02 A6V12955527_----_b A5W00214322A_AB RDF280.V.. Siemens Smart Infrastructure
1) Timer with delay Off / 延时计时器
When P28=1, press and hold icon for more than 3 seconds to enter delay-off timer mode. Use the
+ or – button to change the time up to 23 h and use the () button to confirm the change.
Countdown begins once the unit returns to Normal mode (refer to Parameter list below).
P28=1 按下 3 秒钟进入延时计时器模使用 + 更改时间最大至 23 小时并使用
() 键确认更改。控制器返回标准模式后,倒计时开始(请参考参数列表)。
Changing control parameters / 更改参数
or
Press and hold the + and - buttons simultaneously for more than 3 seconds.
Service level: Release the buttons, and within 2 seconds, press and hold + until Pxx is displayed.
Expert level: Release the buttons, and within 2 seconds, press and hold - until Pxx is displayed.
Press + or - (< or >) to access the desired parameter and the value of the selected parameter is displayed.
Press () to edit the value of the required parameter.
Press + or - to increase / decrease or select a new value of current parameter during editing.
Press () to confirm the new value or press ( ) to cancel the change, and repeat steps 3 to 5 to change more
parameters.
Press ( ) to exit the parameter setting mode.
同时按下 + 3 秒钟以上。
初级参数:松开按键且在 2 秒内按下 + 键直至 Pxx 显示。高级参数:松开按键且在 2 秒内按 键直至 Pxx 显示。
按下 + - 使用 < > 选择参数。所选参数的当前值会显示
按下 使用 编辑所需参数值
按下 + 键,在编辑过程中增加 / 减少或选择当前参数的值
按下 使用 确认更改的值或按下 使用 取消更改。重复步 3 5 更改其他参数。
按下 使用 键)退出参数模式。
Parameter list / 参数列表
Parameter
参数
Description
参数说明
Factory setting
出厂设置
Setting range
设定范围
Adj.
P01* Select VRF mode
选择 VRF 模式
1 0 = AUTO/HEAT/COOL/FAN/Dehumidification
自动/制热/制冷/送风/除湿
1 = HEAT/COOL/FAN/Dehumidification
制热/制冷/送风/除湿
2 = HEAT/COOL/FAN/制热/制冷/送风
3 = HEAT/COOL/制热/制冷
4 = HEAT/FAN/制热/送风
5 = COOL/FAN/Dehumidification/制冷/送风/除湿
6 = COOL/FAN/制冷/送风
P02*
Operation using
operating mode
selector
运行模式切换选项
1 1 = ON – OFF
2 = ON – ECO – OFF
1 = 开启关闭
2
=
开启节能关闭
P03 Temperature display resolution
温度显示分辨率
1 0 = 0.5 K
1 = 1 K
P04 Unit / 单位 0 0 = (Celsius) / (摄氏)
1 = °F (Fahrenheit) / °F (华氏度)
P05 Measured value correction (built-in sensor only)
内置传感器温度测量值修正
0 -5…5 K
P06 Standard display / 标准显示 0 0 = Room temperature / 室内温
1 = Setpoint / 设定值
2 = BUS temperature / 总线温度
P08 Basic setpoint
温度设定值
21 5…40
P09 Minimum setpoint
温度设定值下限
5 5…P10 (P10 = 40 max. / 最大)
P10 Maximum setpoint
温度设定值上限
35 (P09 = 5 min. / 最小) P09…40
P14 Keylock / 按键锁定 0 0 = Unlock / 解锁
1 = Setpoint & fan buttons adjustment only /
仅温度设定值和风速可调
2 = Full lock / 全锁
P27 Operating mode after power failure
断电重启后运行模式
0 0 = Previous operating mode / 前一运行模式
1 = OFF / 关闭
2 = ON (Normal mode) / 开启(标准模式)
P28 Timer with delay Off (0 up to 23 hours, 0.5 h)
延时计时器0 23 小时0.5 小时
1 0 = Disable / 禁用
1 = Enable / 启用
P53* VRF fan type selection
空调风机类型
3 1 = 1-speed /1
2 = 2-speed / 2
3 = 3-speed / 3
4 = 4-speed / 4
5 = 5-speed / 5
6 = 6-speed / 6
7 = 7-speed / 7
P71 Restore factory setting
重载出厂设置
0 0 = Disable / 禁用
1 = Reload start
/
开始重载
P81* Device address / 设备地址 247 1…247
P82* Modbus baud rate
Modbus 波特率
2 1 = 9600 bps
2 = 19200 bps
3 = 38400 bps
4 = 57600 bps
P83* Modbus data frame format
Modbus 数据帧格式
0 0 = 1/8/E/1
1 = 1/8/O/1
2 = 1/8/N/1
3 = 1/8/N/2
P98* Enable Chinese text display
启用中文字符显示
1 0 = Disable
/
禁用
1 = Enable
/
启用
Please record all changes you make. / 请记录您所作出的更改。
To download the latest documentations and applications, go to: / 如需下载最新文档及应用,请访问:https://sid.siemens.com/home
* The parameters are critical and must be set according to the selected equipment during commissioning. Please see Datasheet
(A6V12955494) for further details, such as diagnostic parameters d06, etc. / 这些为重要参数且须在调试过程中根据所选的设备进行设定。
更多信息如诊断参数 d06 等,可参见数据表 (A6V12955494)
Open Source Software / 开源软件 (OSS)
All open source software components used within the product (including their copyright holders and the license conditions) can be found
from the website https://www.siemens.com/download?A6V12983911. / 产品中使用的所有开源软件组件(包括其版权持有者和许可条件)D
均可从网站 https://www.siemens.com/download?A6V12983911 中找到。