Mounting Instructions
Table Of Contents
2/2 2021-10-12 A6V12101240_----_a A5W00134892A_AA RDF270 Siemens Smart Infrastructure
Operating instructions / 操作说明
Overview / 概览
1) Timer with delay Off / 延时计时器
When P28=1, press and hold icon for more than 3 seconds to enter delay-off timer mode. Use the
+ or – button to change the time up to 23 h and use the () button to confirm the change.
Countdown begins once the thermostat returns to Normal mode (refer to Parameter list below).
当 P28=1 时,按下 键 3 秒钟进入延时计时器模式。使用 + 或– 键更改时间最大至 23 小时并使用
() 键确认更改。温控器返回正常模式后,倒计时开始(请参考“参数列表”)。
Changing control parameters / 更改参数
or
或
Press and hold the + and - buttons simultaneously for more than 3 seconds.
Service level: Release the buttons, and within 2 seconds, press and hold + until Pxx is displayed.
Expert level: Release the buttons, and within 2 seconds, press and hold - until Pxx is displayed.
Press + or - (< or >) to access the desired parameter and the value of the selected parameter is displayed.
Press () to edit the value of the required parameter.
Press + or - to increase / decrease or select a new value of current parameter during editing.
Press () to confirm the new value or press ( ) to cancel the change, and repeat steps 3 to 5 to change more
parameters.
Press ( ) to exit the parameter setting mode.
同时按下 + 和 – 键 3 秒钟以上。
初级参数:松开按键且在 2 秒内按下 + 键直至 Pxx 显示。高级参数:松开按键且在 2 秒内按下 – 键直至 Pxx 显示。
按下 + 或 - 键(使用 < 或 > 键)选择参数。所选参数的当前值会显示。
按下 键(使用 键)编辑所需参数值。
按下 + 或 – 键,在编辑过程中增加 / 减少或选择当前参数的值。
按下 键(使用 键)确认更改的值或按下 键(使用 键)取消更改。重复步骤 3 至 5 更改其他参数。
按下 键(使用 键)退出参数模式。
Parameter list / 参数列表
Parameter
参数
Description
参数说明
Factory
setting
出厂设置
Setting range
设定范围
Adj.
更改记
录
P02* Operation using operating mode
selector
使用操作模式图标选择操作模式
1 1 = ON – OFF
2 = ON – FAU ECO – OFF
1 = 开启 – 关闭
2
=
开启 – 新风环保 – 关闭
P14 Keylock / 按键锁定 0 0 = Unlock / 解锁
1 = Setpoint & fan buttons adjustment only /
仅调节设定值和风机按键
2 = Full lock / 全锁
P24* Select bypass (external circulation
only) / 选择旁路(仅外部循环)
0 0 = Disable
/
禁用
1 = Enable
/
启用
P25* Select EXT/INT circulation
选择外部/内部循环
0 0 = Disable
/
禁用
1 = Enable
/
启用
P26
FAU ECO mode / 新风环保模式
Select time ratio within one hour
选择 1 小时内的时间比率
1 1 = 1:5
2 = 2:4
3 = 3:3
4 = 4:2
5 = 5:1
P27 Operating mode after power
failure
断电后操作模式
0 0 = Previous operating mode / 前一操作模式
1 = OFF / 关闭
2 = ON (Normal mode) / 开启(正常模式)
P28 Timer with delay Off (0 up to 23
hours, 0.5 h)
延时计时器(0 至 23 小时,0.5
小时)
1 0 = Disable / 禁用
1 = Enable / 启用
P53* Maximum VRF fan speed
最大空调风速
3
3 = 3-speed / 3 速
8 = DC 0...10 V (ECM fan) / ECM 风机
P55 ECM fan max. output
ECM 风机最大输出
80 % ECM fan min / ECM 风机最小输出…100 %
P56 ECM fan min. output
ECM 风机最小输出
30 % 1 %...ECM fan max. / ECM 风机最大输出
P59 Fan minimum On time (3-speed
fan only)
风机最短启动时间 (仅 3 速风机)
2 min /
2 分钟
1...6 min / 6 分钟
P71 Restore factory setting
重载出厂设置
0 0 = Disable / 禁用
1 = Reload start
/
开始重载
P98* Enable Chinese text display
启用中文字符显示
1 0 = Disable
/
禁用
1 = Enable
/
启用
Please record all changes you make. / 请记录您所作出的更改。
To download the latest documentations and applications, go to: / 如需下载最新文档及应用,请访问:
https://www.downloads.siemens.com/download-center/。
* The parameters are critical and must be set according to the selected equipment during commissioning. Please see Datasheet
(A6V12068497) for further details, such as diagnostic parameters d06, etc. / 这些为重要参数且须在调试过程中根据所选的设备进行设定。
更多信息如诊断参数 d06 等,可参见数据表 (A6V12068497)。