User Manual
79 / 92
Siemens………………..RDF301, RDF301.50..., RDF600KN, RDF600KN/VB, RDF600KN/S Basic Documentation CE1P3171en
Smart Infrastructure 2020-02-21
The application (plant type) and Control Sequence can be adjusted and down-
loaded.
The control parameters, ([Pxx] description) can also be adjusted and down-
loaded. Refer to section 3.13.
5.2 ACS Service and Operating tool
With the ACS tool, the RDF KNX thermostats can be commissioned (physical
address, application, parameters). They can be operated or monitored via bus
during normal operation.
This Manual does not describe how the physical address is defined. Also, it only
gives a brief overview of the main functionality of ACS.
For more information, refer to the ACS online help.
Setting RDF KNX parameters is only supported by ACS Version 5.11 or
higher.
ACS
STOP
Note!