Data Sheet for Product

4 / 20
Siemens RDE100.. Room thermostat with Auto Timer, Option External Input CB1N1422en_10
Building Technologies 2019-02-28
Periodic pump run function
Can only be used when circulating pump or valve is controlled!
This function protects the pump or valve against seizing during longer off periods.
Periodic pump run is activated for 3 minutes every 24 hours at 12:00.
Parameter Pump status
P12 = 0 (Default) Pump run off
P12 = 1 Pump run on
12:00
3 min.
24 h
on
off
1422Z04
Optimum start control
The purpose of optimum start control is to reach a temperature level 0.25 K below
the Comfort setpoint when occupancy according to the time program starts in Auto
timer mode. For that purpose, the heating circuit must be switched on at an earlier
point in time. The extent of forward shift depends primarily on the outside
temperature.
The maximum forward shift on time can be adjusted by parameter P89. A Forward
shift on maximum “0” means the function is disabled.
Parameter Range Factory setting
Forward shift on max
(P89)
0, 0.5,…24 h 0
Optimum stop control
Optimum stop control switches off the heating circuit at the earliest possible point
in time so that the room temperature will lay 0.5 K below the Comfort setpoint when
the time switch changes from Comfort mode to Economy mode in Auto timer mode.
The early shut down maximum time can be adjusted by parameter P90. Early shut
down maximum “0” means the function is disabled.
Parameter Range Factory setting
Early shutdown max
(P90)
0, 0.5,….6 h 0