Data Sheet for Product
13 / 20
Siemens RDE100.. Room thermostat with Auto Timer, Option External Input CB1N1422en_10
Building Technologies 2019-02-28
When holiday mode is activated, symbol appears on the display. The set point
(12 ºC) and the number of days a user is away can be readjusted by pressing
touch keys + and –.
Changing the parameters by the following steps:
· Press + and – simultaneously for 5 seconds
· Release them and parameter "P01" is displayed on the bottom segment
· Press + or – to scroll to the parameter that needs to be adjusted
· Press ok to select this parameter
· Press + or – to adjust the value
· Press ok to confirm the adjusted value
· Press mode to exit the parameters without saving or wait for the program
to exit automatically
Parameter list
Parameter
no.
Description Setting range (default)
P01 Time format
1 = 24:00 hours (default)
2 = 12:00 AM/PM
P02 Selection of °C or °F
1 = °C (default)
2 = °F
P03 Standard temperature display
1 = room temperature
(default)
2 = setpoint
P04 Temperature sensor calibration
-3…3 °C
Step 0.5 °C
(-6…6 °F, step 1 °F)
Default: 0 °C
P06 Comfort setpoint lock
0 = OFF (default)
1 = ON à locked
according to setting in
permanent temperature
setpoint
P08 Economy setpoint lock
0 = OFF (default)
1 = ON à locked
according to setting in
permanent temperature
setpoint
P09 Buzzer
0 = OFF
1 = ON (default)
P10 Show frost protection icon
0 = OFF (default)
1 = ON
P11 Time switch type for auto timer
0 = Individual Days
(default)
1 = All 7 days
2 = 5/2 days
P12 Periodic pump run
0 = OFF (default)
1 = ON
Holiday mode
Parameters