Data Sheet for Product

12 / 20
Siemens RDE100.. Room thermostat with Auto Timer, Option External Input CB1N1422en_10
Building Technologies 2019-02-28
Setting parameter P14 = 1 (X1 External input = External Sensor) and parameter
P15 = 0 (Temperature limitation = Off)
Notes for floor heating temperature control:
- External safety thermostat is needed to prevent overheating of certain floor
heating systems!
- Use of “Comfort setpoint lock” function (Parameter P06) is recommended.
External sensor for Floor heating application with temperature limitation
Refer to Floor Heating application section above when setting parameter P14 = 1
(X1 External input = External Sensor) and parameter P15 = 1 (Temperature
limitation = On). Parameter P16 now allows to limit the maximum temperature.
If the battery symbol appears, the batteries are almost exhausted and should
be replaced. Use alkaline batteries type AAA.
Operating notes
The RDE100.. provides Comfort, Economy, Auto timer and Protection mode. The
difference between Comfort and Economy mode is only the room temperature
setpoint. The changeover between Comfort, Economy and Protection mode is
made either automatically by the auto time switch or by pressing touchkey mode.
When Comfort mode is activated, symbol appears on the display. The setpoint
(20 ºC) can be readjusted by pressing touchkeys + and .
When Economy mode is activated, symbol appears on the display. The setpoint
(16 ºC) can be readjusted by pressing touchkeys + and .
In RDE100.1, a window contact feature is that a user can connect a window
contact to the input X1, . Depending on whether the window contact is
configured to Normally Open or Normally Close (Parameter P14 = 2, Parameter
P17 = 0 or 1), a change in this status will automatically switch the thermostat from
any modes to Economy mode. This feature is good for public area. The factory
setting for this function is Off (disabled).
If the temperature falls below 5 ºC, the unit automatically activates the heating
output. The symbol
appears only, if the icon is enabled via parameter settings.
When Auto timer mode is enabled, the changeover between the operating modes
(Comfort and Economy mode) will take place automatically. There are three
options for time switch setting: individual day, 7 day or 5-2 day. You can select
Comfort or Economy mode in every 15 minutes interval of the day. The 0:00 to
24:00 hour time bar will allow you to set the mode throughout the selected day(s).
Default
value
Day/s Comfort mode Economy mode
Mo (1) – Fr (5) 6:00 – 8:00 hr
17:00 – 22:00 hr
22:00 – 6:00 hr
8:00 – 17:00 hr
Sa (6) – Su (7) 7:00 – 22:00 hr 22:00 – 7:00 hr
Please refer to Operating Instructions CB1B1422, section "Do you want to enter
your own time switch?"
Change of batteries
(only with battery-
powered version
RDE100.1)
Comfort mode
Economy mode
Protection mode
Time switch