s 1 422 Room thermostat with Auto RDE100.. Timer, Option External Input for heating systems · · · · · · · · Room temperature control 2-position / TPI control with On/Off output for heating Optimum Start / Stop Comfort, Economy, Auto timer and Protection mode Auto time switch Adjustable commissioning and control parameters Mains-powered AC 230 V (RDE100) or battery-powered DC 3 V (RDE100.1) Multifunction input (RDE100.1 only) for external floor sensor, keycard contact, etc. Use The RDE100..
· Floor Heating Functions · · · · · · · · · · · Room temperature control via built-in sensor or external input Selection of operating mode with operating mode touchkey Setting auto time switch (individual day, 7 day or 5-2 day) Display of current room temperature or setpoint in °C or °F Touchkey lock (manually) Setpoint lock Periodic pump run Optimum start / stop Comfort temperature limitation by Economy setpoint locked Reloading factory settings for commissioning and control parameters One multifunctional
The external floor temperature sensor is connected to input X1, and acquires the floor temperature. If the floor temperature exceeds the parameterized temperature limit xx ºC (P14 = 1, P15 = 1, P16 = xx ºC), the heating valve is fully closed until the floor temperature returns to a level below the parameterized limit. Typical application is rooms (dry floor).
Periodic pump run function Can only be used when circulating pump or valve is controlled! This function protects the pump or valve against seizing during longer off periods. Periodic pump run is activated for 3 minutes every 24 hours at 12:00. Parameter P12 = 0 (Default) P12 = 1 Pump status Pump run off Pump run on 24 h 3 min. on 1422Z04 off 12:00 12:00 Optimum start control The purpose of optimum start control is to reach a temperature level 0.
Control behavior (P78) The new control algorithm of RDE100.. family offers a choice of control actions that can be configured via parameter P78. This means that optimum control can be selected for every type of application (factory setting “TPI slow”). 2-position, 1 K 2-Position controller with 1 [K] switching hysteresis 2-position, 0.3 K · · · TPI slow 2-Position controller with 0.3 [K] switching hysteresis. For general control situations. Provides a better comfort than 1 [K] switching hysteresis.
Minimum switching on / off time Average period time > 1 minute Approximately 10 minutes Do not use TPI fast for oil boilers or electro mechanical actuators! Type summary Product No. RDE100 RDE100.1 Stock No. S55770-T278 S55770-T279 Features Mains-powered AC 230 V Battery-powered DC 3 V Ordering · When ordering, please indicate product No. / stock No. and description. · Example: Product No. RDE100 Stock No.
Equipment combinations Description Electromotoric actuator Product No. Use with the Data Sheet type of *) Temperature Control SFA21.. 4863 2-Position & TPI slow STA23.. 4884 2-Position & All TPI STP23.. 4884 2-Position & All TPI Damper actuator GDB.. 4634 2-Position & TPI slow Damper actuator GSD.. 4603 2-Position & TPI slow Damper actuator GQD.. 4604 2-Position & TPI slow GXD.. 4622 2-Position & TPI slow QAH11.1 1840 N/A QAA32 ..
Mechanical design The room thermostat consists 2 parts: · Plastic housing which accommodates the electronics, the operating elements and the room temperature sensor · Mounting plate with screw terminals The housing engages in the mounting plate and is secured with a screw. Operation and settings 1) Operating mode touch key 2) Set 3) Ok 4) Touch key for decreasing a value 5) Touch key for increasing a value 8 / 20 Siemens Building Technologies RDE100..
Display 22 21 20 19 18 1 2 17 3 16 5 15 6 7 14 8 9 4 10 11 12 13 # Symbol Description # Symbol Description 1 Indicating that batteries need to be replaced (only with battery-powered version RDE100.
Mounting and installation notes Do not mount the thermostat in niches or bookshelves, not behind curtains, not above or near heat sources, and not exposed to direct solar radiation. Mount about 1.5 m above the floor. Mounting · Mount the thermostat in a clean and dry location without direct air flow from a heating/cooling equipment, and not exposed to drip or splash water Note: When RDE100.. is equipped with either China 86 conduit box or BS4662 UK conduit box, ARG70.
Commissioning notes Commissioning After power is applied, the thermostat carries out a reset during which all LCD segments flash, indicating that the reset was made correctly. After the reset, the thermostat is ready for commissioning by qualified HVAC personnel. The control parameters of the thermostat can be set to ensure optimum performance of the entire system. Please refer to Operating Instructions CB1B1422, section "Do you want to change parameters?".
Setting parameter P14 = 1 (X1 External input = External Sensor) and parameter P15 = 0 (Temperature limitation = Off) Notes for floor heating temperature control: - External safety thermostat is needed to prevent overheating of certain floor heating systems! - Use of “Comfort setpoint lock” function (Parameter P06) is recommended.
Holiday mode When holiday mode is activated, symbol appears on the display. The set point (12 ºC) and the number of days a user is away can be readjusted by pressing touch keys + and –.
P14 X1 External input (only for RDE100.1) P15 Temperature limitation (only for RDE100.1) Max limitation temperature for underfloor heating (only for RDE100.1) Window contact features (only for RDE 100.1) P16 P17 P21 P22 Button scanning rate for the capacitive buttons (RDE100.1 only) Note: a shorter scanning rate means shorter battery life.
Maintenance notes The thermostats are maintenance-free. Disposal The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage. · Dispose of the device through channels provided for this purpose. · Comply with all local and currently applicable laws and regulations. · Dispose of empty batteries in designated collection points.
Technical data Power supply Operating voltage · RDE100 at L - N Frequency Power consumption AC 230 V +10/-15% 50 Hz 8.5 VA / 1 W DC 3 V (2 x 1.5 V alkaline batteries AAA) · RDE100.1 For battery life (RDE100.1), see below (alkaline batteries type AAA). Battery life calculation is based on the touchpad scanning rate during idle time (assuming a user presses 4 touch keys per day with default TPI Slow control): Scanning rate 0.25 s 0.7 year battery life Scanning rate 0.50 s 1.
Environmental conditions Norms and standards Environmental compatibility eu.bac Eco design and labelling directives General Operation Climatic conditions Temperature Humidity Transport Climatic conditions Temperature Humidity Mechanical conditions Storage Climatic conditions Temperature Humidity EU Conformity (CE) As per IEC 60721-3-3 Class 3K5 0…50 °C <95% r.h. As per IEC 60721-3-2 Class 2K3 -25…65 °C <95% r.h. Class 2M2 As per IEC 60721-3-1 Class 1K3 -25…65 °C <95% r.h.
Connection diagrams Lx L Lx 10 A S1 B1 10 A 10 A T X1 Q11 Q11 X1 3V Y1 Nx N Q12 N1 5(2) A N1 Y1 5(2) A Max. Max. Nx RDE100 RDE100.1 N1 Y1 L N Lx Q11, Q12 Q11, Q14 Nx X1 Room thermostat Valve actuator Live, AC 230 V Neutral conductor, AC 230 V Q14 B1 S1 1422A02 Q14 1422A 01 Q12 Live, AC 24 ... 230 V NC contact (for NO valves) NO contact (for NC valves) Neutral conductor, AC 24...
Application examples N1 T T F2 F1 T T Y2 M1 M1 1422S01 Y2 F1 F2 1422S02 T T N1 Room thermostat with direct control of a gas-fired wall-hung boiler N1 Room thermostat with direct control of a gas-fired floor-standing boiler T N1 T F T Y1 Y1 M1 1422S04 1422S03 M1 Room thermostat with direct control of a heating circuit pump (precontrol by manual mixing valve) Room thermostat with direct control of hydronic floor heating system F1 F2 M1 N1 RDE100..
Dimensions All dimensions in mm 85 21.5 0.5 Ø80 83.5 127 Ø60 4.1 7.1 1422M01 Issued by Siemens Switzerland Ltd. Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd, 2013 - 2019 Technical specifications and availability subject to change without notice. 20 / 20 Siemens Building Technologies RDE100..