RDF800KN.., RDD810KN/NF RDF800KN/VB Touchscreen flush-mount room thermostats with KNX communications RDF800KN..
Table of contents 1. About this document ........................................................................... 4 1.1 Revision history ..................................................................................... 4 1.2 Reference documents ............................................................................ 4 1.3 1.3.1 1.3.2 1.3.3 Before you start ..................................................................................... 5 Copyright .....................................
.8 Fan control (RDF800KN.., RDF800KN/VB only) ................................... 46 3.9 Multifunctional input, digital input.......................................................... 50 3.10 Handling faults ..................................................................................... 52 3.11 3.11.1 3.11.2 3.11.3 3.11.4 3.11.5 3.11.6 3.11.7 3.11.8 KNX communications........................................................................... 53 S-mode...........................................
Edition 04 Date 2020-02-21 03 2017-02-17 02 01 2015-06-08 2014-11-20 1. About this document 1.1 Revision history Changes · Update KNX interface · RDF800KN/VB · Update condensation monitor · Update heartbeat Minor changes and corrections First edition 1.2 Subject Ref Touchscreen flush-mount [1] room thermostats with KNX communications [2] [3] KNX Manual [4] Synco and KNX (see www.siemens.
1.3 1.3.1 Before you start Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.2 Quality assurance This document was prepared with great care. · The contents of this document are checked at regular intervals. · Any corrections necessary are included in subsequent versions.
1.4 Target audience, prerequisites This document assumes that users of the RDF800KN../RDF800KN/VB/RDD810KN.. thermostats are familiar with the ETS and/or Synco ACS tools and can use them. It is also assumed that these users are aware of the specific conditions associated with KNX. In most countries, specific KNX know-how is conveyed through training centers certified by the KNX Association (see www.knx.org/). For reference documentation, see section 1.2. 1.
2. Summary 2.1 Types Product no. Stock no. Application RDF800KN S55770-T350 RDF800KN/VB S55770-T429 Fan coil, universal heat pump Fan coil, universal heat pump Fan coil, universal heat pump Heating RDF800KN/NF2) RDD810KN/NF2) S55770-T335 S55770-T336 Operating voltage Control outputs On/Off 3-pos 21) 11) 2 1) 11) 21) 11) AC 230 V Suitable for Round or square conduit boxes Round or square conduit boxes Square conduit boxes 2) 13) - 1) Select: On/Off or 3-position.
Features · Operating modes: Comfort, Economy and Protection · Backlit display · AC 230 V operating voltage In addition for RDF800KN..
2.4 Touchscreen display User interface The RDF800KN.., RDF800KN/VB and RDD810KN/NF room thermostats have a touchscreen (segment type) user interface. The thermostat displays only the room temperature value or any alarm in Screen Saver mode. To start any operation or change settings, touch the screen to display all available operating icons available in Selection Screen mode. Ten seconds after the last operation, the thermostat returns to Screen Saver mode.
2.5 Integration with KNX bus The touchscreen room thermostats can be integrated as follows: · · · · Into Synco living using group addressing (ETS) Into Desigo using group addressing (ETS) or individual addressing Into third-party systems using group addressing (ETS) With Synco 700 system using LTE mode (easy engineering) The following KNX functions are available: · Central time program and setpoints. For example, when using the RMB795B central control unit.
Synco topology Legend Synco 700 Synco living RDF800KN.., RDF800KN/VB RDD810KN/NF OZW772 RMZ792-B QAW...
2.6 Equipment combinations Description Cable temperature sensor or changeover sensor, cable length 2.5 m NTC (3 kW at 25 °C) Room temperature sensor NTC (3 kW at 25 °C) Cable temperature sensor, cable length 4 m NTC (3 kW at 25 °C) On/Off actuators Notes: Data Sheet QAH11.1 1840 QAA32 1747 QAP1030/UFH 1854 Condensation monitor QXA2100/ QXA2101 A6V10741072 Electromotoric On/Off actuator SFA21.. 4863 MVI../MXI.. A6V11251892 SUA.. 4832 STA23.. 4884 STP23..
2.7 Accessories Description Product no./SSN no. Changeover mounting kit (50 pcs per package) Plastic mounting spacer for RDF800KN, RDF800KN/VB to increase the headroom in the conduit box by 10 mm Conduit box for RDF800KN/NF and RDD810KN/NF ARG86.3 Data Sheet N3009 ARG70.3 N3009 ARG71/S55770-T137 N3009 Single mounting frame*), ivory white (for RDF800KN/NF and RDD810KN/NF only) KNX power supply 160 mA KNX power supply 320 mA KNX power supply 640 mA ARG800.
3. Functions 3.1 Room temperature control General note: Parameters Information for setting the control parameters (e.g. P01) is described in section 3.14. Room temperature control The thermostat acquires the room temperature using its built-in sensor, external room temperature sensor (QAA32), or external return air temperature sensor (QAH11.1), and maintains the setpoint by delivering actuator control commands to the heating and/or cooling equipment.
Time of day via bus can be displayed on the 2nd line of the LCD display on the thermostat by setting P07 to either 3 or 4. The display is either in 12- or 24-hour format. Time of day via bus The information can be received from a Synco controller with time master functionality or any other KNX device if the corresponding communication object is bound.
When you touch OFF, the thermostat changes to ON first and then returns to Comfort or Economy mode. Then it displays the setpoint adjustment screen. Touch +/– to adjust the room temperature setpoint. Notes: · · · In Economy mode, the icon does not display since the setpoint is not adjustable. In Protection mode, both the and icons do not display since both setpoint and fan speed are not adjustable. On universal applications (P52 = 0), the icon does not display.
· the window contact is active (open window) · "Window state" is sent using the bus, e.g. from a KNX switch. See note*). Note: *) Refer to section 3.2.1 for details regarding the window contact and presence detector. 17 / 94 Siemens Smart Infrastructure RDF800KN..
3.2.1 Source for change of operating mode ACS Source Local operation using operating mode icon Bus command Room operating mode Influencing the operating mode The operating mode can be influenced in different ways. The source of the effective room operating mode state can be monitored using the "Cause" diagnostic data point in the ACS tool, bus operator unit RMZ792-B or web server OZW772.
Auto Timer mode with time scheduler using the bus If a time scheduler is available, e.g. from the central control unit, Auto Timer mode is active. The thermostat automatically changes between Comfort and Economy mode according to the time scheduler using the bus. The display shows the Auto Timer mode icon . Touch the operating mode icon to change to another operating mode.
The “window contact” function is also available using the KNX signal "Window state", e.g. from a KNX switch. Room operating mode: Window state Note: Only one input source can be used, either a local input X1/X2 or the KNX bus. User operations are ineffective and OFF is displayed if the operating mode “window contact” is active, or if "Window state" is sent using the bus.
3.2.2 Communication example The following example shows a typical application of a central time scheduler in conjunction with local control of the room operating mode. The room operating mode in the room of a building is determined by the time scheduler. Window contact and presence detector are fitted in this room.
Time scheduler Room operating mode Comfort Precomfort Economy Protection Presence detector Occupied Unoccupied Window contact room 3 Window open Window closed Comfort Effective room operating mode room 3 Economy Protection 22 / 94 Siemens Smart Infrastructure RDF800KN..
3.3 3.3.1 Room temperature setpoints Description Setpoint mode Touch the icon when it is available on the display and press +/– to adjust the desired room temperature setpoint. Comfort mode The factory setting for the Comfort basic setpoint is 21 °C. It can be changed in the thermostat’s EEPROM using P08 or the bus with the communication object "Comfort basic setpoint". The last option selected is always used.
P10) of the inactive sequence. For example, the thermostat is in the heating sequence and runs with the heating setpoint. When the room temperature reaches P09, the thermostat switches to cooling mode and runs with the cooling setpoint, as long as the room temperature does not drop below P10. Example 5°C 21°C P10 25°C P09 40°C Cooling setpoint adjustable: 25…40 °C Heating setpoint adjustable: 5…21 °C Economy mode Use P11 and P12 to adjust the Economy mode setpoints.
3.3.
· Notes on setpoint adjustment (LTE mode with Synco only) · · · · · · · Setpoint priority, Setpoint Master RMB · Setting the Comfort basic setpoint resets the runtime Comfort setpoint to the basic setpoint. Central setpoint shift is used for summer or winter compensation. Setpoint shift does not affect the parameter setpoints in P08, P11, P12 and P33. Local shift and central shift are added together. Only applies to Comfort and Economy setpoints. Protection setpoints are not shifted centrally.
Remote configuration RDF800KN.., RDF800KN/VB only All DIP switches must be set to OFF (remote configuration, factory setting) in order to select an application using the commissioning tool. Remote configuration, using one of the following tools (factory set) · Synco ACS · ETS4 DIP switches For more information, see the following sections: · · · · Section 3.4.1 “Applications for fan coil systems (RDF800KN.., RDF800KN/VB only)”; Section 3.4.2 “Applications for universal systems (RDF800KN..
3.4.1 Applications for fan coil systems (RDF800KN..
3.4.2 Applications for universal systems (RDF800KN..
3.4.3 Applications for heat pump systems (RDF800KN..
3.4.
3.5 Heating/cooling changeover using bus Additional functions The heating/cooling changeover information can only be received using the bus, if the control sequence is set to automatic heating/cooling changeover (P01 = 3), and no local input X1/X2 is assigned with this function. When the required information is missing (e.g. due to problems with data communication, or a power failure), the thermostat operates in the last valid room operating mode (heating or cooling).
Manual heating/cooling changeover If manual heating/cooling changeover is set (P01 = 2), heating/cooling mode cannot be changed using the bus, changeover sensor or switch; it will remain in the manually selected mode. External/return air temperature sensor The thermostat acquires the room temperature through its built-in sensor, external room temperature sensor (QAA32), or external return air temperature sensor (QAH11.1) connected to multifunctional input X1 or X2.
The table below shows the relation between parameter, temperature source and temperature display: OFF OFF 10...50 ˚C External temp. sensor available No Yes No Source for display of room temperature Built-in sensor External sensor Built-in sensor 10…50 ˚C Yes Built-in sensor P51 Output control according to Built-in sensor External temp. sensor Built-in sensor Built-in sensor + limit by external sensor Floor temp.
3.6 3.6.1 Control sequences Sequences overview using P01 (RDF800KN.., RDF800KN/VB only) The main control sequence (such as the water coil sequence of the fan coil unit) can be set via P01. The following sequences can be activated in the thermostats (each without or with auxiliary heating). The available sequences depend on the application (via the DIP switch, see section 3.4).
3.6.2 Application mode The behavior of the thermostat can be influenced by a building automation and control system (BACS) via the bus using the "Application mode" command. Application mode With this signal, cooling and/or heating mode can be enabled or disabled. Application mode is supported in LTE mode and S-mode. The RDF800KN../RDF800KN/VB/RDD810KN.. room thermostats support the following commands: No.
Heating OR cooling With 2-pipe applications, the control sequence state is determined by the application mode (see section 3.6.3) and by the state of the heating/cooling changeover signal (using the local sensor or the bus), or fixed according to the selected control sequence (P01 = heating (0)/cooling (1)).
3.6.3 2-pipe fan coil unit (RDF800KN.., RDF800KN/VB only) On 2-pipe applications, the thermostat controls a valve in heating/cooling mode with changeover (automatically or manually), heating only, or cooling only. Factory setting is “Cooling only” (P01 = 1). On/Off control Control sequence On/Off output The diagrams below show the control sequence for 2-position control.
3.6.4 Heating or cooling with auxiliary heater 2-pipe fan coil unit with electric heater (RDF800KN.., RDF800KN/VB only) On 2-pipe applications with electric heater, the thermostat controls a valve in heating/cooling mode with changeover, heating only, or cooling only plus an auxiliary electric heater. Cooling only is factory-set (P01 = 1) with electric heater enabled (P13).
On/Off control Control sequence ON/OFF output The diagrams below show the control sequence for 2-position. Heating mode Cooling mode (automatic changeover = heating or heating only) (manual/auto.
3.6.5 4-pipe fan coil unit (RDF800KN.., RDF800KN/VB only) Heating and cooling On 4-pipe applications, the thermostat controls 2 valves in heating and cooling mode, heating/cooling mode by manual selection (P01 = 2), or heating and cooling mode with changeover. Heating and cooling mode (P01 = 4) is factory-set. On/Off control The diagrams below show the control sequence for 2-position control.
3.6.7 Compressor applications (RDF800KN.., RDF800KN/VB only) For compressor applications, proceed as follows: 1. Set the corresponding basic application 2. Disable the fan (P52) or set the fan speed (P53) The following applications are available: Application for compressor Set basic See section application 1-stage compressor 2-pipe 3.6.3 for heating or cooling 1-stage compressor and electric heater 2-pipe and electric 3.6.
2) In case of manual changeover (P01 = 2), the first heating sequence is disabled to prevent heating (electric heater) and cooling (coil) at the same time W = setpoint in Comfort mode WHeatEco/Prot = setpoint heating in Economy or Protection mode WCoolEco/Prot = setpoint cooling in Economy or Protection mode YR = radiator sequence E1 = electric heater sequence 4-pipe applications On 4-pipe applications, the Comfort setpoint (w) is in the middle of the dead zone, between the heating and the cooling seque
3.7 Control outputs 3.7.1 Overview of control outputs Different control output signals are available. They must be defined during commissioning (see below). Control output Product no. RDF800KN.., RDF800KN/VB 2-position 2-position PWM Y1, Y2 (2 x SPST) Q11, Q12, Q14 (1 x SPDT) RDD810KN/NF *) On/Off control signal (2-position) Overview 3-position DC 0…10 V --- Y1, Y2*) (1 x / ) --- --- --- --- Only applies to 2-pipe applications.
Synchronization · · · Heating output control signal (2-position) RDD800KN/NF only When the thermostat is powered up, a closing command for the actuator running time + 150% is delivered to ensure that the actuator fully closes and synchronizes to the control algorithm. When the thermostat calculates either the fully closed or fully open position, the actuator's running time is extended + 150% to ensure the right actuator position is synchronized to the control algorithm.
3.8 Fan control (RDF800KN.., RDF800KN/VB only) The fan operates in automatic mode or at the selected speed in manual mode. In automatic mode, the fan speed depends on the setpoint and the current room temperature. When the room temperature reaches its setpoint, the control valve closes and the fan switches off or stays at fan speed 1 according to the setting of P15 (fan stage in dead zone Comfort) and P60 (fan kick).
3-speed fan control with modulating heating/cooling control The individual switching points for ON of each fan speed can be adjusted via P55…P57. The fan speed switch off point is 20% below the switch-on point. The diagrams below show fan speed control with modulating PI control.
Fan operation in dead zone (fan kick) In automatic fan mode and with the room temperature in the dead zone, the control valve is normally closed and the fan disabled. With the "Fan kick" function, the fan can be released from time to time at low speed for minimum on-time (see above) even if the valve is closed. This function can be used to avoid damage from moisture due to a lack of air circulation, or to allow a return air temperature sensor to acquire the correct room temperature.
Clean filter reminder Fault information The "Clean filter reminder" function counts the fan operating hours and displays message " FIL" to remind the user to clean the fan filter as soon as the threshold is reached. This does not impact the thermostat's operation, which continues to run normally. The function is set using P62 (default = OFF (0)). The "Clean filter reminder" function can be removed using +/ – when viewing alarms on the INFO page.
3.9 Multifunctional input, digital input The thermostat has two multifunctional inputs X1 and X2. An NTC type sensor, such as the QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals. The functionality of the inputs can be configured using P38 or P39 for X1 and P40 or P41 for X2. The current temperature or the state of inputs X1 or X2 is available on bus for monitoring purposes. The parameters can be set to the following values: No.
No. 5 Function of input Enable electric heater Enable electric heater 6 Description Digital input to enable/disable the electric heater using remote control. Enabling the electric heater is also possible using the bus. In this case, the function must not be assigned to local input X1 or X2. See section 3.2.1. Digital input to signal an external fault (e.g. dirty air filter). Fault Fault information Type X1/X2 DI RDF.. RDD..
3.10 Handling faults Room temperature out of range When the room temperature is out of the measuring range (that is, above 49 °C or below 0 °C), the limiting temperature flashes. In addition, the heating output is activated if the current setpoint is not set to "OFF", the thermostat is in heating mode and the temperature is below 0 °C. For all other cases, no output is activated. The thermostat resumes Comfort mode after the temperature returns to the measuring range.
3.11 KNX communications The RDF800KN../RDF800KN/VB/RDD810KN.. KNX room thermostats support communications as per KNX specification. S-mode Standard mode; engineering using group addresses. LTE mode Logical Tag Extended mode, for easy engineering, used in conjunction with Synco. 3.11.1 S-mode This mode corresponds to KNX communications. Connections are established via ETS by assigning communication objects to group addresses. 3.11.2 LTE mode LTE mode was specifically designed to simplify engineering.
· For a detailed description of KNX (topology, bus supply, function and setting of LTE zones, filter tables, etc.), see "Communication using the KNX bus for Synco 700, 900 and RXB/RXL, Basic Documentation" [6]. · LTE mode data points and settings are described in the Synco Application Manual [12]. · To engineer and commission a specific system, use the Synco700 planning and commissioning protocol (XLS table in HIT, [7]). Engineering and commissioning 3.11.
The zones to be defined are as follows: Geographical zone (space zone) Zone in which an RDF800KN../RDF800KN/VB/RDD810KN.. KNX room thermostat is physically located. Other room-specific devices may also be located in this zone. (Apartment . Room. Subzone) Apartment = ---, 1...126 Room = ---, 1...63 Subzone = fix 1 Information exchanged in this zone is related specifically to the device’s operating mode, setpoints, room temperature, and so on.
3.11.4 Example of heating and cooling demand zone The building is equipped with Synco controls on the generation side and with RDF../RDU../RDG.. room thermostats on the room side. Konnex TP1 Controller 1 RMB795 Controller 3 Controller 2 RDF.. Controller 4 RDU.. Controller 5 RDG..
Object [KNX obj. Nr.] Room operating mode: Time switch [12] Room operating mode: Preselection [7] Application mode [31] Reducing the bus load I/O Minutes Default value Receive 31 Comfort Receive 31 Auto Receive 31 Auto Individual zones can also be disabled (out of service) using a control parameter if they are not required. In disabled zones, the LTE signal is no longer periodically sent, and therefore reduce bus load. 3.11.
The table below shows the error code and default alarm texts.
3.12 Communication objects (S-mode) 3.12.1 RDF800KN.., RDF800KN/VB Overview Page Object no. and name 15 15 1 3 14 44 Outdoor temperature 18 12 Room operating mode: Time switch1) 7 Room operating mode: Preselection1) 20 Room operating mode: Window state 45 Room operating mode: Presence detector 22 Room temperature: Comfort basic setpoint 23 Room temperature: Comfort setpoint 18 16 16 25 25 36 Object no.
3.12.2 RDD810KN/NF Overview Page Object no. and name 15 15 1 3 14 44 Outdoor temperature 18 12 Room operating mode: Time switch1) 7 Room operating mode: Preselection1) 20 Room operating mode: Window state 45 Room operating mode: Presence detector 22 Room temperature: Comfort basic setpoint 23 Room temperature: Comfort setpoint 18 16 16 25 25 36 Thermostat Object no.
3.12.3 Description of communication objects Obj 1 Object name System time Function Type/length Flags Time and 19.001 CWU date 8 Byte System time for display on the room thermostat. See P07 (3 or 4) 3 Time of day Time and 10.001 CWU date 3 Byte Another object for receiving the time of day for display on the thermostat. See P07 (3 or 4) 4 Fault information Alarm 219.001 CT Info 6 Byte Common alarm output. If an alarm occurs, the alarm number is transmitted 5 Fault state Faulty/ 1.
Obj 27 Object name Function Type/length Flags Cooling output 0…100% 5.001 CRT primary 8 bit Indicates the position of the cooling actuator of the first stage. E.g. 2-pipe with electric heater application: Output of cooling coil 29 Enable electric Enable/ 1.003 CWU heating Disable 1 bit An electric heater can be disabled with this communication object (e.g. to meet tariff regulations). The same function is also available using local multifunctional input X1/X2 (P38 or P40).
3.13 Communication objects (LTE mode) 3.13.1 RDF800KN.., RDF800KN/VB Overview Geographical zone A.R.S Room operating mode: Time switch (Time switch zone) X.1.1/X.Y.1 Application mode Room operating mode: Preselection Geographical zone A.R.S X.Y.1 Room temperature output Comfort setpoint Setpoints heating Setpoints cooling Fan speed Setpoint shift heating Setpoint shift cooling Heat distr. zone Heating coil energy demand heating coil Heating/cooling changeover Ref. distr.
3.13.2 RDD810KN/NF Overview Geographical zone A.R.S Room operating mode: Time switch (Time switch zone) X.1.1/X.Y.1 Application mode Room operating mode: Preselection Geographical zone A.R.S X.Y.1 Room temperature output Comfort setpoint Setpoints heating Setpoint shift heating Heat distr. zone Heating coil energy demand heating coil Broadcast Fault transmission Fault information Fault text Outdoor air temp. zone Outdoor temperature fix 31 64 / 94 Siemens Smart Infrastructure RDF800KN..
3.14 Control parameters A number of control parameters can be readjusted to optimize control performance. This can be done on the thermostat using the HMI, or the tool. These parameters can also be set during operation without opening the unit. In the event of a power failure, all control parameter settings are retained, see section 3.14.
Configuring parameters After entering the correct password, the screen displays as follows. Touch / to advance or return to the desired parameter and use +/- to select the desired available value. Refer to section 3.14.3 for Service level parameters; refer to section 3.14.4 for Expert level parameters. Resetting parameters The factory setting for the control parameters can be reloaded using P71, by setting the value to ON. Refer to section 3.14.4 for P71.
Range 2-pipe: 1 = cooling only 0= 1= 2= 3= 4= RDF800KN..
Heat P-band Xp/switching differential Cool P-band Xp/switching differential 2K 0.5…6 K ü ü 1K 0.5…6 K x ü P33 P34 Dead zone Comfort mode Setpoint differential 2K 2K 0.5…5 K 0.5…5 K x ü P35 P36 Integral action time Tn 45 min 16 °C 0...120 min 10…25 °C x x x ü ü ü 28 °C 27…40 °C x ü 0 = --- (no function) 1 = room temp ext.
Factory setting Range RDD810KN/NF RDF800KN.., RDF800KN/VB Dependencies x ü P52 x ü P52, Appl. P52, P53 P52, P53 P52, P53 Parameter Name Expert level P53 Fan speeds 3-speed P54 Fan overrun time 60 s 1 = 1-speed 2 = 3-speed 0...360 s P55 Fan speed switching point high Fan speed switching point med Fan speed switching point low 100% 80...100% x ü 65% 30..75% x ü 10% 1...
d01 Application number d02 X1 state d03 X2 state d05 Test mode for checking the Y1/Y2 actuator's running direction3) 3) NONE = (no application) 2P = 2-pipe 2P3P = 2-pipe 3-position 2PEH = 2-pipe with electric heater 4P = 4-pipe 0 = not activated (for DI) 1 = activated (DI) 0…49 °C = current temp. value (for AI) 00 = H/C input shorted 100 = H/C input open 0 = not activated (for DI) 1 = activated (DI) 0…49 °C = current temp.
4. Handling 4.1 Mounting and installation Mount the room thermostat on the conduit box. Do not mount on a wall in niches or between bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount it approximately 1.5 m above the floor. Mounting / dismounting · Do not apply excessive force on screws! The deformation of the mounting frame may lead to improper connections and operation of the unit.
4.2 Before powering up (only for RDF800KN.., RDF800KN/VB) Commissioning Before powering up, set the DIP switches for the desired application. Do one of the followings: · For remote setup via the tools, set all DIP switches to OFF; · For local setup, set the DIP switches to select applications (see table below).
LCD Parameter Range RDF800KN/VB only ) 2: Fan speed 1 Cool only 0: --- no function 1: Ext/return Temp (AI) 2: H/C changeover (AI/DI) 3: Window contact (DI) 4: Dew point sensor (DI) 5: Enable electric heater (DI) 6: Fault input (DI) 7: Monitor input (digital) 8: Monitor input (temp) 10: Presence detection (DI) Functionality of X1 Functionality of X2 Factory setting 3 1 Operating action of X1 Normally open (NO) Normally closed (NC) Normally open (NO) Operating action of X2 - End of wizard - For
Note: Control parameters An external KNX bus power supply is required if an RDF800KN../RDF800KN/VB/RDD810KN.. KNX room thermostat is connected directly to a tool (ACS or ETS) using KNX interface. The thermostat's control parameters can be set to ensure optimum performance of the entire system. The parameters can be adjusted using · Local HMI · Synco ACS · ETS The control parameters of the thermostat can be set to ensure optimum performance of the entire system (see section 3.14).
4.3 Operation The following pages can be displayed by touching the icon, depending on priority: alarm/service reminder, manual H/C changeover, basic Information about room and outdoor temperature. See the previous sections in this document for the following operations: temperature setpoints, fan speed, operating modes, parameter mode, programming mode, etc. 4.3.1 Alarm/Service reminder If any alarm is displayed ( reminder.
4.3.3 INFO page This INFO page provides information about room temperature ( temperature ( ) and outdoor ), if available from the KNX bus. Room temperature Outdoor temperature If there is no active alarm or manual heating or cooling changeover is disabled, (P01 ≠ 2), only the INFO page displays. 4.4 Remote operation The RDF800KN../RDF800KN/VB/RDD810KN.. KNX room thermostats can be operated from a remote location using the OZW772 web server, a RMZ792-B bus operating unit or the ACS tool. 4.
ETS 5. Supported KNX tools 5.1 ETS ETS is an engineering tool and is used to fully commission the RDF800KN../RDF800KN/VB/RDD810KN.. KNX room thermostats. ETS can implement the following functions: · · · · Define and download the physical address Define and download the application (plant type, control sequence) Set up and download the thermostat's control parameters Set up and download group addresses This document does not describe how to operate ETS and how to set up a device.
5.1.2 Notes: 1. 2. Open the project in ETS and select a device. Click Parameters tab, and adjust the control parameters as follows: 3. The Plant type (application), Control Sequence and other control parameters ([Pxx] description) can be downloaded. For more details on control parameters, see section 3.14. · · · 5.
5.2.1 Parameter settings in ACS In the ACS program, select Plant à Open to open the plant. To start the parameter settings, select Applications à Plant engineering. The application and control parameters can be adjusted and downloaded. Column Line no. contains the parameter number as displayed in the parameter table. Refer to section 3.14.
5.2.2 Operation and monitoring with ACS In the ACS program, select Plant à Open to open the plant. To start operation and monitoring, select Applications à Plant operation. ACS Parameter settings in ACS Notes: Plant diagram in ACS The ACS tool supports parameter settings even during normal operation. To change a control parameter, double click the parameter under Standard popcard to make the settings. · Make sure you have logged on with sufficient access right.
The ACS tool provides standard plant diagrams for RDF800KN../RDF800KN/VB/RDD810KN..
Plant type Application Configuration – Fan operation: Not disabled Heating only Application Configuration (P52 <> 0) – Fan operation: Disabled (P52 = 0) Fan coil unit main/secondary – Control sequence: Auto c/o (P01 = 3) – Fan operation: Not disabled (P52 <> 0) Main/secondary – Control sequence: Auto c/o – Fan operation: Disabled (P01 = 3) (P52 = 0) – Floor heating limit temperature (P51=OFF) – Floor heating limit temperature (P51≠OFF) 82 / 94 Siemens Smart Infrastructure RDF800KN..
Operation and monitoring with OZW772 web server 5701Z01a 5.2.3 Web browser Internet / Intranet OZW772.. USB Ethernet Ethernet Router KNX TP1 The OZW772 web server enables you to operate a Synco HVAC system from a remote location (computer or smartphone) – using the HomeControl app. The start page shows the most important data points. Navigating through menus and paths enables you to access all data points quickly and correctly.
6. Connection 6.1 Connection terminals L N SELV 3171A01 RDF800KN.., RDF800KN/VB X1 X2 CE+ CE- M Q1 Q2 Q3 Y1 L, N Q1 Q2 Q3 Y1,Y2 Y2 X1, X2 M CE+ CE- Operating voltage AC 230 V Control output "Fan speed 1 AC 230 V" Control output "Fan speed 2 AC 230 V" Control output "Fan speed 3 AC 230 V" Control output "Valve" AC 230 V (NO, for normally closed valves), output for compressor or electric heater Multifunctional inputs for temperature sensor (e.g. QAH11.
Application RDF800KN.., RDF800KN/VB Connection diagrams L KNX AC 230 V 10 A S1 S2 B1 B2 X1 L Y2 N1 Y1 N Q1 Q2 Q3 2-pipe/heating or cooling – On/Off CE+ CE- X2 M I II III V1 M1 5(2)A Max . N 5(2)A Max . 2-pipe/heating or cooling – 3-position – Y1 = open – Y2 = close 3171A12 6.2 N1 M1 V1 V1, V2 E1 C1, C2 S1, S2 B1, B2 V1 5(2)A Max . 2-pipe and electric heater/ heating or cooling and electric heater V1 5(2)A Max .
7. Mechanical design 7.1 General The thermostats consist of two parts: · Front panel with electronics, operating elements and built-in room temperature sensor. · Mounting base with power electronics. Note: RDF800KN/NF and RDD810KN/NF require additional mounting frames to complete the installation and are only suitable for square conduit boxes (confirming to BS 4662 standard). RDF800KN is suitable for round conduit boxes (conforming to CEE/VDE), or square conduit box (confirming to BS 4662 standard).
7.2 Dimensions Dimensions in mm RDF800KN/NF and RDD810KN/NF for square conduit boxes only 87 / 94 Siemens Smart Infrastructure RDF800KN..
RDF800KN, RDF800KN/VB for round conduit boxes 88 / 94 Siemens Smart Infrastructure RDF800KN..
ARG800.1 single mounting frame for RDF800KN/NF and RDD810KN/NF 89 / 94 Siemens Smart Infrastructure RDF800KN..
8. Power supply Caution Outputs for RDF800KN.., RDF800KN/VB STOP Note! Outputs for RDD810KN/NF Caution Inputs KNX bus Technical data Rated voltage Overvoltage category Frequency Power consumption AC 230 V III 50/60 Hz Max. 6.0 VA/2.1 W No internal fuse! External preliminary protection with max C 10 A circuit breaker required in all cases. Fan control Q1, Q2, Q3-N Rating min. and max. res (ind.) AC 230 V Min 5 mA, max.
Operational data Switching differential, adjustable Heating mode (P30) Cooling mode (P31 for RDF800KN.., RDF800KN/VB, RDD810KN only) Setpoint setting and range Comfort (P08) Economy (P11-P12 for RDF800KN.., RDF800KN/VB,RDD810KN) (P11 for RDD810KN/NF) Protection (P65-P66) Multifunctional input X1/X2 for RDF800KN..
Wiring cross section on L, N, Q1, Q2, Q3, Y1, Y2 Housing front color Weight without/with packaging for RDF800KN.., RDF800KN/VB, RDD810KN Weight without/with packaging for RDD810KN/NF *) Reference documentation Min 1.5 mm2 RAL 9001 white RAL 9004 black 0.155/0.255 kg 0.145/0.245 kg The documents can be downloaded from http://siemens.com/bt/download. Handbook for Home and Building Control - Basic Principles (https://my.knx.
Index 1 1-speed fan......................................................... 47 3 3-position control signal ...................................... 44 3-speed fan......................................................... 47 A Applications overview ......................................... 26 Auto Timer mode ................................................ 19 Automatic heating/cooling changeover .......... 32, 35 Automatic heating/cooling changeover using bus 32 B Basic application ...........................
Presence detector............................................... 16 Proportional band ............................................... 14 Protection mode/Standby .................................... 16 Purge function .................................................... 33 PWM .................................................................. 44 R Radiator applications .......................................... 41 Reload factory settings .......................................