Data Sheet for Product

9
Siemens A6V11881086_en--_b
Smart Infrastructure 2020-05-20
Control parameters
Parameter Description Factory setting Setting range
P01 Control sequence RDD510 = 0 0:= Heating only
1:= Cooling only
P05 Sensor calibration 0 K -5…+5 K
P06 Standard temperature display 0 0:= Room temperature
1:= Setpoint
P09 Minimum setpoint in Comfort mode 5 5…40
P10 Maximum setpoint in Comfort mode 35 5…40
P14 Keylock function 0 0:= No lock
1:= Full lock
2:= Partial lock
P27 Operating mode settings upon power
down
0 0:= Return to previous operating
mode or user settings
1:= Protection mode
2: = Comfort mode
P28 Timer with delay Off 0 0:= Users to set on-time duration
1 to 23:= Preset with a fixed on-
time in hours
P30 Switching differential in heating mode 1 K 0.5 … 6 K
P31 Switching differential in cooling mode 1 K 0.5 … 6 K
P65 Protection heating setpoint 8 OFF, 5 Wcool
pro
;
Wcool
pro
=40 max.
P66 Protection cooling setpoint OFF OFF, Wheat
pro
…40;
Wheat
pro
=5 min.
P71 Reload factory setting OFF OFF:= Disable
ON:= Reload start
“---” is displayed for 3 seconds
while reloading