User Manual
If there are thermostatic radiator valves in the reference room, they must be set to their
fully open position.
Maintenance
The controller is maintenance-free.
Sensor calibration
If the temperature on the display does not agree with the room temperature effectively
measured, the temperature sensor can be recalibrated. For that purpose, both buttons
+
and must be pressed simultaneously for 3 seconds. Then, the temperature
displayed can be changed by a maximum of +/- 3 Kelvin by pressing the
+
and
-
buttons. Five seconds after the last push of a button, the controller will automatically
return to the normal operational statuses.
Change of batteries
(only with battery-
powered versions)
If the battery symbol appears, the battery power is almost exhausted and the batteries
should be replaced.
Technical data
Power supply
Operating voltage
• RDD10 at L - N AC 230 V +10/-15 %
• RDD10.1 DC 3 V (2 x 1.5 V AAA Alkaline batteries)
Frequency (RDD10) 50 or 60 Hz
Power consumption (RDD10) 4VA
Battery life (RDD10.1) > 1 years (AAA Alkaline batteries)
Control output Q12 (N.C. contact)
Rating RDD10 (AC 230 V) max. 5(2) A
Rating RDD10.1 (AC 24...250 V) max. 5(2) A
Control output Q14 (N.O. contact)
Rating RDD10 (AC 230 V) max. 5(2) A
Rating RDD10.1 (AC 24...250 V) max. 5(2) A
Control outputs
Switching differential SD 1 K
Setpoint setting range 5…35 °C (normal operation)
0 (OFF) and 5…35 °C (energy saving mode)
Increments 0.5 °C
Factory setting normal operation 20 °C
Factory setting energy saving mode 8 °C
Setting range of operating mode
changeover time 0.5…24 h
Increment 0.5 h
Factory setting 0 h (not activated)
Functional data
Operation to IEC 721-3-3
Climatic conditions class 3K5
Temperature 0…+50 °C
Humidity <95 % r. h.
Transport to IEC 721-3-2
Climatic conditions class 2K3
Temperature -25…+60 °C
Humidity <95 % r. h.
Mechanical conditions class 2M2
Storage to IEC 721-3-1
Climatic conditions class 1K3
Temperature -25…+60 °C
Humidity <95 % r. h.
Environmental conditions
5/8
Building Technologies Room temperature controllers CE1N3031en
HVAC Products 24.02.2005