User Manual

3/10
Siemens RCU50... Room Thermostat CE1N3045en
Building Technologies 2017-11-15
Q
[
]
%
100
0
W2 W
W1
12,5K 12,5K
+12,5K
(K)
T
[
]
(V)
10
5
-12,5K
0
3041D04
W Original setpoint
W1 Highest setpoint at 10 V input
W2 Lowest setpoint at 0 V input
(K) Setpoint shift
(V) Input voltage
The setpoint shift is limited within the range of the unit of 8 °C (frost protection)
to 30 °C.
The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3) is
used by the room thermostat to switch from heating to cooling mode, or vice versa.
When the water temperature lies above 28 °C, the room thermostat switches to heating
mode, below
16 °C it switches to cooling mode.
CM
HM
T
W
[
]
16 28
M
CM Cooling mode
HM Heating mode
M Operating mode
T
W
Water temperature
The room temperature setpoint can be limited in increments of 1 Kelvin by making use
of the minimum and maximum limitation facility. Arbitrary setpoint readjustments can
thus be prevented.
Operating modes
The following operating modes are available:
Normal operation is activated when the operating mode selector is set to “ “ (RCU
50.1) and the external operating mode changeover switch is not activated. In normal
operation, the room thermostat maintains the adjusted setpoint.
Frost protection mode can be activated either
by manually switching to standby (RCU50.1)
by activating the external operating mode changeover switch, provided DIP switch
no. 1 is set to OFF
If the room temperature falls below 8 °C, the room thermostat will automatically switch
to frost protection mode. In that case, the heating valve opens and the room
temperature is maintained at a setpoint of 8 °C. The setpoint adjusted by the user will
be ignored.
Energy saving mode can be activated either
by manually switching to energy saving mode “ (RCU50.1)
by activating the external operating mode changeover switch, provided DIP switch
no. 1 is set to ON
In energy saving mode, the setpoint of heating is 16 °C and the setpoint of cooling
28 °C, independent of the position of the setpoint knob.
.
.
Automatic changeover
(RCU50 and RCU50.1)
Energy saver
Normal operation
Frost protection mode
(RCU50 and RCU50.1)
Energy saving mode