User Manual

4/8
Siemens Room Temperature Controllers CE1N3048en
Building Technologies 2017-11-14
Mechanical design
The unit consists of two parts:
A plastic housing which accommodates the electronics, the operating elements and
the built-in room temperature sensor
A mounting base
The housing engages in the mounting base and snaps on.
The base carries the screw terminals. The DIP switches are located at the rear of the
housing.
3048Z01
1
2
3
1 Room temperature setpoint knob
2 Setting facility for minimum setpoint limitation
(in increments of 1 K)
3 Setting facility for maximum setpoint limitation
(in increments of 1 K)
DIP switch
no.
Meaning Position ON Position OFF
1 Operating mode changeover via
external switch
Changeover from normal op-
eration or standby to energy
saving mode
Changeover from normal operation
or energy saving to standby
1)
2 Operating action of switch for ex-
ternal operating mode changeover
Changeover activated when
contact of switch is closed
(N.O.)
1)
Changeover activated when con-
tact of switch is open
(N.C.)
3 Switching different or P-band 1 K in heating mode
0.5 K in cooling mode
4 K in heating mode
1)
2 K in cooling mode
1)
4 Dead zone in normal operation 2 K
1)
5 K
5 Signal output Y1 (heating) ON / OFF
1)
PWM
6 Signal output Y2 (heating or cool-
ing)
ON / OFF
1)
PWM
7 Operating action of output Y2 Cooling
1)
Heating
8 PWM signal interval for outputs
heating and cooling
(DIP switch 7 set on position ON)
Y1 (heating) 240 s
1)
90 s
Y2 (cooling) 240 s (not selectable)
PWM signal interval for outputs
heating 2 stage
(DIP switch set on position OFF)
Y1 (heating) 240 s (not selectable)
Y2 (heating) 240 s
1)
90 s
1) Factory setting
Setting and operating
elements
Legend
Set of DIP switches
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.