User Manual

6/8
Siemens Room Temperature Controllers CE1N3041en
Building Technologies 2017-11-14
Warning!
No internal line protection for supply lines to external consumers (Y1, Y2)
Risk of fire and injury due to short-circuits!
Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
The room controller is maintenance-free.
Disposal
The device is considered an electronic device for disposal in terms of the Euro-
pean Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Operating voltage
AC 230 V
+10 %, -15 %
Frequency 50/60 Hz
Power consumption max. 6 VA
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line re-
quired under all circumstances
Setpoint setting range 8...30 °C
Max. control deviation at 25 °C max. ° 0.7 K
Switching differential heating SDH or P-band
(selectable)
1 K or 4 K
Switching differential cooling SDC or P-band
(selectable)
0,5 K or 2 K
Dead zone X
dz
in normal operation (selectable) 2 K or 5 K
Setpoint «Energy saving mode », heating 16 °C
Setpoint « Energy saving mode », cooling 28 °C
Setpoint «Standby » 8 °C
Integration time Tn 10 min
Control outputs Y1, Y2
Voltage
Current
Cycle time PWM (selectable for Y1)
PWM or ON / OFF
AC 230 V +10 %
- 15 %
0.02…1 A
240 s or 90 s
Status input D1 and GND
Contact sensing
Insulation against mains
SELV DC 6-15 V / 3-6 mA
4 kV
Perm. cable length with copper cable 1.5 mm
2
for status input D1 80 m
Operation
Climatic conditions
Temperature
Humidity
to IEC 60721-3-3
class 3K5
0... 50 °C
; 95 % r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
to IEC 60721-3-2
class 2K3
, 25...+70 °C
<95 % r.h.
class 2M2
Maintenance
Power supply
Functional data
Environmental
conditions