User Manual
4/8
Siemens Room Temperature Controllers CE1N3041en
Building Technologies 2017-11-14
Equipment combinations
Type of unit Type reference Data sheet
*)
Motoric on/off actuator
SFA21...
4863
Thermal actuator (for radiator valve)
STA21...
4893
Thermal actuator (for small valve 2,5 mm)
STP21...
4878
Air damper actuators
GCA32…1
4613
*) The documents can be downloaded from http://siemens.com/bt/download.
Mechanical design
The unit consists of two parts:
∂ A plastic housing which accommodates the electronics, the operating elements and
the built-in room temperature sensor
∂ A mounting base
The housing engages in the mounting base and snaps on.
The base carries the screw terminals. The DIP switches are located at the rear of the
unit.
3041Z01
1
4
2
3
1 Operating mode selector (RCU10.1)
(normal operation, energy saving mode and standby)
2 Room temperature setpoint knob
3 Setting facility for minimum setpoint limitation
(in increments of 1 K)
4 Setting facility for maximum setpoint limitation
(in increments of 1 K)
DIP switch
no.
Meaning Position ON Position OFF
1 Operating mode changeover via
external switch
Changeover from normal op-
eration or standby to energy
saving mode
Changeover from normal operation
or energy saving to standby
1)
2 Operating action of switch for ex-
ternal operating mode changeover
Changeover activated when
contact of switch is closed
(N.O.)
1)
Changeover activated when con-
tact of switch is open
(N.C.)
3 Switching different or P-band 1 K in heating mode
0.5 K in cooling mode
4 K in heating mode
1)
2 K in cooling mode
1)
4 Dead zone in normal operation 2 K
1)
5 K
5 Signal output Y1 (heating) ON / OFF
1)
PWM
6 Signal output Y2 (heating or ON / OFF
1)
PWM
Setting and operating
elements
Legend
Set of DIP switches