User Manual
7
Smart Infrastructure
A6V11562464_en--_a
2019-09-19
Technical data
Power supply
Operating voltage AC 230 V (+10/-15%)
Frequency 48…63 Hz
Power consumption 5 VA
Radio parameters
Frequency band 2.4…2.4835 GHz
Maximum radio-frequency power 15 dBm
Thread standard IEEE 802.15.4
Thread channel 11-26
Switching capacity of relays
Voltage AC 24…230 V
Current Q11- Q12 Max. 5 A
Q11- Q14 Max. 8 (2) A
Q21- Q22 Max. 5 A
Q21- Q24 Max. 8 (2) A
WARNING
No internal fuse.
External preliminary protection with max. C 16 A circuit breaker in the supply lines
required under all circumstances.
External protection for incoming cable
Circuit breaker Max. 16 A
Circuit breaker tripping characteristic Type B, C or D to EN 60898 and EN 60947
Contact life at AC 230 V
At 8 A res.
Guided value:
1 x 10
5
cycles
Insulation strength
Between relay contacts and coil
Between relay contacts (same pole)
AC 5,000 V
AC 1,000 V
Electrical connections
Connection terminals Screw terminals
For solid wires 2 x 1.5 mm
2
For stranded wires 1 x 2.5 mm
2
(Min. 0.5 mm
2
)
Ambient conditions and protection classification
Safety class as per EN60730 Class II
Degree of protection of housing as per EN
60529
IP30
Classification as per EN 60730
Function of automatic control devices
Operation altitude
Degree of contamination
Overvoltage category
Type 1
< 3000 m
2
III