Smart Thermostat Receiver RCR114.1 Smart Thermostat Receiver works with RDS110.R. ● ● ● ● A6V11562464_en--_a 2019-09-19 Mains-powered receiver AC 230 V Configurable via DIP switch Communicate with RDS110.
Use The RCR114.1 works as a router-eligible end device (REED) in the network created by RDS110.R. Functions RCR114.1 can be configured via the DIP switch on its backside to be a relay box or wireless repeater. Relay box RCR114.1 is installed within the network coverage of RDS110.R.
If RCR114.1 is installed too far away from RDS110.R, another RCR114.1 (works as a wireless repeater) should be added in between to extend the network coverage. See Mounting [➙ 4] for details. Note: 1. DIP switch 2 is reserved for internal use only. 2. One RDS110.R can pair up with at most 3 repeaters and 6 relays to extend the network coverage. 3. You cannot mannually turn ON / OFF a RCR114.1. Mechanical design The RCR114.
Equipment combinations Room thermostats Product number Stock number Description RDS110.R S55772-T103 Smart Thermostat Wireless Product number Stock number Description SSA911.01TH S55181-A101 Radiator valve act. THREAD Wireless actuator Note: the RDS110.R cannot control a relay box and a valve actuator in parallel. Wireless receiver Product number Stock number Description RCR114.
● Choose the location to ensure largely interference-free reception. When mounting the receiver, observe the following: – Do not mount in a control panel – Do not mount on metallic surfaces – Do not mount near 2.4 GHz wireless electronic devices such as PCs, WiFi routers, microwaves, etc.
Operation RCR114.1 has one physical button for user operation. Operation Device action Short press (if idle) Join network and attempt binding Short press (if connected) Device identification Short press (in other status) No action Long press Factory reset to idle Maintenance The receiver is designed for maintenance-free operation. Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage.
Technical data Power supply Operating voltage AC 230 V (+10/-15%) Frequency 48…63 Hz Power consumption 5 VA Radio parameters Frequency band 2.4…2.4835 GHz Maximum radio-frequency power 15 dBm Thread standard IEEE 802.15.4 Thread channel 11-26 Switching capacity of relays Voltage AC 24…230 V Current Q11- Q12 Max. 5 A Q11- Q14 Max. 8 (2) A Q21- Q22 Max. 5 A Q21- Q24 Max. 8 (2) A WARNING No internal fuse. External preliminary protection with max.
Ambient conditions and protection classification Climatic ambient conditions Transport (packaged for transport) as per EN 60721-3-2 Storage as per EN 60721-3-1 Operation as per EN 60721-3-3 Transport/ Storage: Temperature -25...60 °C (-13... 158 °F) Air humidity 5...95% r.h. (non-condensing) Operation: Temperature 0...50 °C (23... 122 °F) Air humidity 5...95% r.h.
Example 1: Loads = AC 230 V Y1 HVAC equipment Y2 DHW / Dehumidifier / Humidifier KT Relay Example 2: Loads Y1, Y2 ≠ AC 230 V Application examples Applications Smart Infrastructure Gas boiler Electric boiler Floor heating with valve Radiator with pump 9 A6V11562464_en--_a 2019-09-19
Applications Floor heating with pump Electric radiator Electric floor heating Fan with electric heating Domestic hot water boiler 10 Smart Infrastructure N1 RDS110.R N2 RCR114.1 F1, F2 Limit thermostats K1 Heat generator (e.g.
Dimensions Smart Infrastructure 11 A6V11562464_en--_a 2019-09-19
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 12 Smart Infrastructure Document ID A6V11562464_en--_a Edition 2019-09-19 © Siemens Switzerland Ltd, 2019 Technical specifications and availability subject to change without notice.