Data Sheet for Product
Table Of Contents
6
Siemens
A6V11562464_en
--
_b
Smart Infrastructure
2021
-
07
-
16
Commissioning
LED indication on RCR114.1
The RCR114.1 has one LED to indicate its status.
Device status LED status
Idle Solid yellow
Connecting to RDS110.R Flashing green
Successful connection Solid green
Thread® network works, but communication with
RDS110.R failed
1)
Flashing red
Thread® network failure
2)
Solid red
Factory reset Alternating red and green
1. Reconnection is performed automatically or manually.
2. Reconnection can only be performed manually.
Manual network reconnection
1. Check if the RDS110.R is powered on and in normal operation.
2. If the reconnection still fails, delete the RCR114.1 from the device list of the RDS110.R,
then press and hold the button on the RCR114.1 for 8 seconds to re-add the
RCR114.1 to the device list.
Operation
The RCR114.1 has one physical button for user operation.
Operation Device action
Press (if idle) Join network and attempt binding
Press (if connected) Device identification
Press (in other status) No action
Press and hold Factory reset to idle
Maintenance
The receiver is designed for maintenance-free operation.