Data Sheet for Product

5
Siemens
A6V11562464_en
--
_b
Smart Infrastructure
2021
-
07
-
16
Notes
Security
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
Mounting
Note the following when mounting the unit:
The device is suitable for wall and surface mounting.
Enclose the conductors in a conduit when surface mounting.
Reserve sufficient free space for ventilation (see the following picture).
Avoid direct sunlight.
Observe to allowed ambient conditions.
Install the receiver close to the RDS110.R if possible. The communication range in a
building is typically 60 m in open space. Note that the range can vary because walls,
floors, wireless interference and other factors may reduce the signal strength.
Choose the location to ensure largely interference-free reception. When mounting the
receiver, observe the following:
Do not mount in a control panel
Do not mount on metallic surfaces
Do not mount near 2.4 GHz wireless electronic devices such as PCs, WiFi routers,
microwaves, and so on
Do not mount near constructional elements with fine metal or large metallic struc-
tures such as a distribution box
Wiring
The AC 230 V mains supply line must have an external circuit breaker with a rated cur-
rent of no more than 10 A.
Ensure that wiring, protection and grounding comply with local regulations.
Observe local regulations for wiring size and the rated value of the installed overcurrent
protection device.
Disconnect from power supply before removing the unit from its mounting plate.
Ensure that receiver is not connected to power during wiring.