Notes
Security
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
● Observe national provisions and comply with the appropriate safety regulations.
Mounting
● Note the following when mounting the unit:
● The device is suitable for wall and surface mounting.
● Enclose the conductors in a conduit when surface mounting.
● Reserve sufficient free space for ventilation (see the following picture).
● Avoid direct sunlight.
● Observe to allowed ambient conditions.
● Install the receiver close to the RDS110.R if possible. The communication range in a
building is typically 60 m in open space. Note that the range can vary because walls,
floors, wireless interference and other factors may reduce the signal strength.
● Choose the location to ensure largely interference-free reception. When mounting the
receiver, observe the following:
– Do not mount in a control panel
– Do not mount on metallic surfaces
– Do not mount near 2.4 GHz wireless electronic devices such as PCs, WiFi routers,
microwaves, and so on
– Do not mount near constructional elements with fine metal or large metallic struc-
tures such as a distribution box
Wiring
● The AC 230 V mains supply line must have an external circuit breaker with a rated cur-
rent of no more than 10 A.
● Ensure that wiring, protection and grounding comply with local regulations.
● Observe local regulations for wiring size and the rated value of the installed overcurrent
protection device.
● Disconnect from power supply before removing the unit from its mounting plate.
● Ensure that receiver is not connected to power during wiring.