User Manual
CE1N3025en
12.06.2003
Siemens Building Technologies
HVAC Products
3
025
Room Temperature
Controller
RCC50.1
for two-pipe fan coil units
Modulating PI control
Output for DC 0…10 V valve actuator
Outputs for three-speed fan
Automatic heating / cooling changeover
Operating modes: normal and energy saving or OFF
Operating mode changeover input for remote control
Function for avoiding damage resulting from moisture
Operating voltage AC 24 V
Use
Typical use:
• Control of the room temperature in individual rooms that are heated or cooled
with two-pipe fan coil units.
• For opening or closing a DC 0…10 V valve actuator
• For switching a three-speed fan.
Suited for use in systems with
• automatic heating / cooling changeover
• continuous heating or cooling operation.