User Manual

8/10
Siemens Room temperature controller CE1N3022en
Building Technologies 2017-11-14
Disposal
The device is considered an electronic device for disposal in terms of the Euro-
pean Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Operating voltage
AC 230 V
+10/-15 %
Frequency 50/60 Hz
Power consumption max. 6 VA
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line re-
quired under all circumstances
Control outputs Q1, Q2, Q3
Rating
AC 230 V
max. 600 VA
Control output Y11 (N.O. contact)
Rating
AC 230 V
max. 300 VA
Control output Y12 (N.C. contact)
Rating
AC 230 V
max. 300 VA
Control output Y21 (N.O. contact)
Rating
AC 230 V
max. 1250 VA
Signal input B1 for return air sensor QAH11.1, Safety class II
NTC resistor 3kΩ at 25°C
Signal input B2 for changeover-sensor QAH11.1, Safety class II
NTC resistor 3kΩ at 25°C
Status input D1 and GND
Contact sensing
Insulation against mains
SELV DC 6-15V / 3-6 mA
4 kV, extra insulation
Perm. cable length with copper cable 1.5 mm
2
for connection to terminals B1, B2 and D1 80 m
Setpoint setting range 8...30 °C
Max. control deviation at 25 °C max. ° 0.7 K
Switching differential in heating mode SDH (select-
able)
1 K or 4 K
Switching differential in cooling mode SDC (select-
able)
0.5 K or 2 K
Dead zone Xdz in normal operation 2 K or 5 K
Setpoint «Energy saving mode », heating 16 °C
Setpoint « Energy saving mode », cooling 28 °C
Setpoint «Standby » 8 °C
Operation
Climatic conditions
Temperature
Humidity
to IEC 60721-3-3
class 3K5
0…+50 °C
<95 % r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
to IEC 60721-3-2
class 2K3
-25…+70 °C
<95 % r. h..
class 2M2
Power supply
Operational data
Environmental conditions