Data Sheet for Product

CE1N1197en
2019
-10-09
Smart Infrastructure
1
197
RAM-TR RAM-TW
Strap-on Thermostats
-TR...
Electromechanical TR and TW
Temperature control or limitation with single-pole changeover microswitch
Switching capacity contact connection 1-2: 0.2...16 A, AC 250 V
contact connection 1-3: 0.2...2.5 A, AC 250 V
Mounting choices: surface-mounted on pipes or storage tanks
Use
Typical applications:
In heat generation plant (control or supervision of the water temperature, control of
pumps, valves, etc.)
For general use in heating, ventilation and air conditioning plant
Function
When the externally adjustable setpoint of the control thermostat (TR) is reached on
rising medium temperature, contact connection 1-2 changes over to 1-3.
When the internally adjustable switch-off temperature of the thermal reset limit thermo-
stat (TW) is reached on rising medium temperature, contact connection 1-2 changes
over to 1-3.
When the temperature of the medium falls by the value of the switching differential, the
contact connection reverts (1-2 closes, 1-3 opens).
Changeover switch
(S.P.D.T)

Summary of content (4 pages)