Data Sheet for Product

4/6
Siemens Thermal reset limit thermostat RAK-TW CE1N1203en
Building Technologies 2018-03-23
Technical data
Switching capacity
Nominal voltage
Nominal current I (I
M
) contact connection 1-2
contact connection 1-3
AC 24…250 V
0.1...16 (2.5) A
0.1… 6 (2.5) A
External fuse
16 A
Life expectancy at nominal rating
min. 100 000 switching cycles
Safety class
I to EN 60 730
Degree of protection:
IP43 and IP65 to EN 60 529
Temperature setting range
RAK-TW.5000HS
RAK-TW.5000S-H
RAK-TW.5010S-H
(with tool)
5... 65 °C
-10…50 °C
Thermal switching differential
5 K
Product standard
EN 60730
-x
DIN EN 14597 (TW1197)
1)
EU Conformity (CE)
CE1T1206xx
1)
Radio interference protection
click rate N 5 to EN 55 014
Operation
Max. temperature on bulb
Ambient temperature at the housing
Humidity
Mechanism
Storage and transport
Ambient temperature
Humidity
class 3K5 to IEC 60 721
-3-3
max. switching temperature
+ 25 K
max. 80 °C (T80)
< 95 % r.h.
class 3M2 to I
EC 60 721-3-3
class 2K3 to IEC 60 721
-3-2
-
25…+70 °C
< 95 % r.h.
Max. temperature socket
125 °C
Degree of pollution
2 to EN 60 730
Controlled medium
Water, air, oil
Calibration temperature
30 °C
Manufacturing deviation
±3 °C for RAK-TW.5010S-H
Calibrated for ambient temperature at the
switching mechanism and capillary tube
0 °C /
-6 °C for RAK-TW.5000S-H
RAK-TW.5000HS
22 °C to DIN EN 14597
Time constant in: water
oil
air
<45 s to DIN EN 14597
<60 s to DI
N EN 14597
<120 s to DIN EN 14597
Electrical connections
Earth connection
Cable gland
Push In
2)
terminals for wires
6 x
0.75...2.5 mm²
Push In
2)
terminals for wires
2 x
0.75...2.5 mm²
M16 x 1.5 mm
External wiring flexible cord
designed
to be connected with
unprepared condu
ctors or prepared
conductors, e.g. ferrules
The product environmental declaration CE1E1186de
1)
contains data on environmentally
compatible product design and assessments (RoHS compliance, materials
composition, packaging, environmental benefit, disposal).
Switching mechanism
Directives and
Standards
Environmental
conditions
Calibration
Connections
Environmental
compatibility