Data Sheet for Product
1
206
Limit Thermostats
RAK-TB.1..M
Electromechanical TB
• Limit thermostat with single-pole changeover microswitch
• Switching capacity contact connection 11-12 16 (2.5) A, AC 250 V
Terminal for alarm contact connection 11-13 0.5 A, AC 250 V
• Time constant conforming to DIN EN 14597
• 3
mounting choices: pipe, pocket or wall mounting
• Switch-off temperature can be checked through the viewing window in the
housing
• Internal reset facility covered by removable threaded nipple
• Push-in terminals for fast installation
Use
Typical applications:
• Heat generation plant
• For general use in heating, ventilation and air conditioning plant
• Underfloor heating systems (RAK-TB.1400-M)
Function
When the switch-off temperature is reached, contact connection 11-12 changes over to
contact connection 11-13 (alarm) and the thermostat remains tripped in this position.
When the temperature of the medium falls below the value of the switching differential,
the limit thermostat (TB) must be manually reset after removal of the threaded nipple.
If the probe has cooled down to a temperature below approx. -20°C, the control
current circuit opens, however, automatically closes again, when the temperature rises.
CE1N1206en
2014-07-30
Building Technologies