User Manual

Disposal
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Switching capacity
Nominal voltage
Nominal current I (I
M
) contact connection 11-12
contact connection 11-13
AC 24…250 V
0.1...16 (2.5) A
2 (0.4) A (terminal for alarm)
External fuse
16 A
Life expectancy at nominal rating
min. 300 switching cycles
Safety class
I to EN 60 730
Degree of protection:
IP 43 to EN 60 529
Internally adjustable switch
-off temperature
RAK-TB.1400
S-M
RAK-TB.1410B-M
RAK-TB.1420S-M
45...60 °C
50...70 °C
65...80 °C
Thermal switching differential (all types)
10 ± 5 K
Product standard
EN 60730
-x
DIN EN 14597
EU Conformity (CE)
CE1T1206xx
1)
Radio interference protection
click rate N 5 to EN 55 014
Operation
Max. temperature on bulb
Ambient temperature at the housing
Humidity
Mechanism
Storage and transport
Ambient temperature
Humidity
class 3K5 to IEC 60 721
-3-3
max. switch
-off temperature + 25 K
max. 80 °C (T80)
< 95 % rH
class 3M2 to IEC 60 721
-3-3
class 2K3 to IEC 60 721
-3-2
-
25…+70 °C
< 95 % r.h.
Max. temperature socket
125 °C
Degree of pollution
2 to EN 60 730
Controlled medium
Water, oil, air
Manufacturing deviation
+0 /-6 °C
Calibrated for ambient temperature at the switching
mechanism and capillary tube to DIN
EN 14597
RAK-TB.1400S-M
RAK-TB.1410B-M
RAK-TB.1420S-M
22 °C
22 °C
22 °C
22 °C
Time constant in:
water
oil
air
<45 s to DIN
EN 14597
<60 s to DIN
EN 14597
<120 s to DIN EN 14597
Electrical connections
Earth connection
Cable entry gland
P
ush In
2)
terminals for wires
6 x
0.75...2.5 mm²
Push In
2)
terminals for wires
2 x
0.75...2.5 mm²
M16 x 1.5 mm
External wiring flexible cord
Type M attachment (designed to be
connected with prepared condu
c
tors,
e.g. ferrules)
Switching mechanism
Directives and Standards
Environmental conditions
Calibration
Connections
3/4
Siemens Limit thermostats RAK-TB CE1N1206en