User Manual
Disposal
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
• Dispose of the device via the channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.
Technical data
Switching capacity
Nominal voltage
Nominal current I (I
M
) contact connection 11-12
contact connection 11-13
AC 24…250 V
0.1...16 (2.5) A
2 (0.4) A (terminal for alarm)
External fuse
16 A
Life expectancy at nominal rating
min. 300 switching cycles
Safety class
I to EN 60 730
Degree of protection:
IP 43 to EN 60 529
Internally adjustable switch
-off temperature
RAK-TB.1400
S-M
RAK-TB.1410B-M
RAK-TB.1420S-M
45...60 °C
50...70 °C
65...80 °C
Thermal switching differential (all types)
10 ± 5 K
Product standard
EN 60730
-x
DIN EN 14597
EU Conformity (CE)
CE1T1206xx
1)
Radio interference protection
click rate N ≤5 to EN 55 014
Operation
Max. temperature on bulb
Ambient temperature at the housing
Humidity
Mechanism
Storage and transport
Ambient temperature
Humidity
class 3K5 to IEC 60 721
-3-3
max. switch
-off temperature + 25 K
max. 80 °C (T80)
< 95 % rH
class 3M2 to IEC 60 721
-3-3
class 2K3 to IEC 60 721
-3-2
-
25…+70 °C
< 95 % r.h.
Max. temperature socket
125 °C
Degree of pollution
2 to EN 60 730
Controlled medium
Water, oil, air
Manufacturing deviation
+0 /-6 °C
Calibrated for ambient temperature at the switching
mechanism and capillary tube to DIN
EN 14597
RAK-TB.1400S-M
RAK-TB.1410B-M
RAK-TB.1420S-M
22 °C
22 °C
22 °C
22 °C
Time constant in:
water
oil
air
<45 s to DIN
EN 14597
<60 s to DIN
EN 14597
<120 s to DIN EN 14597
Electrical connections
Earth connection
Cable entry gland
P
ush In
2)
terminals for wires
6 x
0.75...2.5 mm²
Push In
2)
terminals for wires
2 x
0.75...2.5 mm²
M16 x 1.5 mm
External wiring flexible cord
Type M attachment (designed to be
connected with prepared condu
c
tors,
e.g. ferrules)
Switching mechanism
Directives and Standards
Environmental conditions
Calibration
Connections
3/4
Siemens Limit thermostats RAK-TB CE1N1206en
Building Technologies 2014-07-30