Data Sheet for Product

4/6
Siemens Safety limit thermostat RAK-ST CE1N1204en
Smart Infrastructure 2020-08-04
Technical data
Switching capacity
Nominal voltage
Nominal current I (I
M
) contact 11-12
contact 11-13
AC 24…250 V
0.
1...16 (2.5)
2 (0.4) A (terminal for alarm)
External fuse
16 A
Life expectancy at nominal rating
Estimated value for B
10d
M
in. 300switching cycles
B
10d
= 250‘000 (DIN EN ISO 13849-1)
Safety class
I to EN 60 730
Degree of protection:
IP43 or IP54 to EN 60 529
Fixed switch-off temperature
RAK-ST.010FP-M
RAK-ST.020FP-M
RAK-ST.030FP-M
95 °C
100 °C
110 °C
Switch
-off temperature, internally adjustable RAK-
RAK-ST.1300P-M
RAK-ST.1310P-M
RAK-ST.1430S-M
RAK-ST.1385M
RAK-ST.1600MP
(with tool)
110
...130 °C
90...110 °C
80...100 °C
40…70 °C
95…130 °C
Thermal switching differential
RAK-ST.1385M
RAK-ST.1600MP
RAK-ST.010FP-M / RAK020FP-M /
RAK030FP-M/ RAK1430S-M
RAK-ST.1300P-M / RAK1310P-M
10
K
Product standard
EN 6
0730-x
DIN EN 14597 (STB1196)
1)
EU Conformity (CE)
CE1T1204xx
1)
Radio
interference protection
C
lick rate N 5 to EN 55 014
Operation
Max. temperature on bulb
Ambient temperature at the housing
Humidity
Mechanism
Storage a
nd transport
Ambient temperature
Humidity
C
lass 3K5 to IEC 60 721-3-3
switch
-off temperature + 25 K
max. 80 °C (T80)
< 95 % r.h.
class 3M2 to IEC 60 721
-3-3
class 2K3 to IEC 60 721
-3-2
-
25…+ 70 °C
< 95 % r.h.
Max. temperature socket
125 °C
Degree of pollution
2 to EN 60 730
Controlled medium
Water, oil, air
Ambient temperature compensation for switching
mechanism and capillary tube
22 °C DIN EN 14 597
The product environmental declaration CE1E
1186
1)
contains data on environmentally
compatible product design and assessments (RoHS compliance, materials composition,
packaging, environmental benefit, disposal).
Switching mechanism
Directives and
Standards
Environmental
conditions
Environmental
compatibility
.
.
.