Data Sheet for Product

3/4
Siemens Room Thermostats RAA11 CE1N3561en
Building Technologies 2016-03-25
Only authorised personnel may open the unit to perform service.
The unit must be isolated from the mains supply before opening.
When installing the unit, fix the baseplate first, then hook on the thermostat body and
make the electrical connections. Then fit the cover and secure it also refer to separate
mounting instructions.
The thermostat must be mounted on a flat wall.
The local electrical regulations must be complied with.
If there are thermostatic radiator valves in the reference room, set them to their fully
open position.
Warning!
No internal line protection for supply lines to external consumers (Y1, Y2)
Risk of fire and injury due to short-circuits!
· Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
The room thermostat is maintenance-free.
The diaphragm is filled with environmentally friendly gas.
The thermostat housing is made of plastic.
Ordering
Disposal
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
· Dispose of the device via the channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.
Technical data
Switching capacity
Voltage
Current
Frequency
AC 24...250 V
0.2…6(2.5) A
50 or 60 Hz
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line required under all
circumstances
Screw terminals for 2 x 1.5 mm
2
(min. 0.5 mm
2
)
Switching differential SD
£1K
Setpoint setting range 8…30 °C
Operation
Climatic conditions
Temperature
Humidity
Pollution degree
to IEC 60721-3-3
Class 3K5
0…+50 °C
<95 % r.h.
normal, to EN 60730-1
Transport / Storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
to IEC 60721-3-2
Class 2K3/1K3
-20…+50 °C
<95 % r.h.
Class 2M2
EU Conformity (CE)
CE1T3561xx
*)
RCM Conformity
CE1T3561en_C1
*)
AC 250 V
Maintenance
Mechanical design
Type (ASN) Part number (SSN) Description
RAA11 S55770-T219 Room thermostat RAA11
Power supply
Operational data
Environmental conditions
Industry standards