Mounting Instructions

2 / 2 10.08.2012 M1597xx 74 319 0872 0 a Siemens Building Technologies
0
Pipe support
(i.e. external mounting brackets)
1
5
9
7
Z
1
4
12 Nm
!
Counter-hold
QVE2000.0xx QVE2100.0xx Color of the connection wires
OUT
3
41
V
OUT
Q
GNDIN
1
5
9
8
Z
0
6
A
GNDIN
3
4
1
Pin Color
1 brown
3 blue
4 black
Dimensions in mm
1597M0
1
ca. 60G
C
A
G
B
E
D
Type (ASN)
Nominal
diameter
Measuring
range [l/min]
A
[mm]
B
[mm]
C
[mm]
D
[mm] Ø
E
[mm]
G
[inch]
QVE2x00.010 DN 10 1.8…32 35 41 81 12 19
QVE2x00.015 DN 15 3.5…50 36.6 43 87 16 22
QVE2x00.020 DN 20 5.0…85 36.6 45 105 20 27 G1
QVE2x00.025 DN 25 9.0…150 50 47 120 26 34 G1¼
2012 Siemens Switzerland Ltd