Data Sheet for Product
2 / 6
Siemens Flow sensor QVE2x00.0xx CM1N1597en
Building Technologies 2015-02-18
Use
The flow sensor is suited to continuously measure flow or monitor liquids
such as hot water, heating water, or standard water-glycol mixes in HVAC
plants and applications. The sensors can be used in automation and control
systems as control sensor or measured value sensor.
Type summary
Type /
ASN
Product nu
m
ber
(SSN)
Nominal
width dia
[mm]
Measuring range
[l/min] [m
3
/h]
Output signal
DC
QVE2000.010 S55720-S189 DN 10 1.8…32 0.1…1.92 0…10 V
QVE2000.015 S55720-S190 DN 15 3.5…50 0.2…3.0 0…10 V
QVE2000.020 S55720-S191 DN 20 5.0…85 0.3…5.1 0…10 V
QVE2000.025 S55720-S192 DN 25 9.0…150 0.5…9.0 0…10 V
QVE2100.010 S55720-S193 DN 10 1.8…32 0.1…1.92 4…20 mA
QVE2100.015 S55720-S194 DN 15 3.5…50 0.2…3.0 4…20 mA
QVE2100.020 S55720-S195 DN 20 5.0…85 0.3…5.1 4…20 mA
QVE2100.025 S55720-S196 DN 25 9.0…150 0.5…9.0 4…20 mA
Ordering
When ordering, please specify the quantity, type, and product name.
Example:
1 flow sensor QVE2000.010
Scope of delivery:
- Flow sensor with external thread connection
- 2 x inserted O-ring
- Straight, 3-pin plug M12x1 with cable, 2 m
- Mounting instructions
Type Stock number Designation
ASN SSN Product designation
QVE2000.01
0
S55720-S189 Flow sensor
Delivery