Basic Documentation

Mainten
ance
Troubleshooting
6
A6V11160936_en--_c 35 | 40
6.3 Troubleshooting
Error Description 0-10 V output Modbus
QSA2700D
Replace sensor module
when:
1. it is broken;
2. it reaches its
lifetime.
Present 0 V (2
s) and 10 V (2
s) one by one in
turn
Value of register
209 changes
from 0 to 1
QSA2700D Check for:
1. the communication
error between
sensor module and
product MCU;
2. missing sensor
module.
Present 0 V (5
s) and 10 V(5 s)
one by one in
turn
Value of register
209 changes
from 0 to 2
QSA2700D
Warning of possible
inaccurate
measurement
Present the
measured value
Value of register
209 remains 0
without change
QSA2700 Red permanently on
Error 1, replace sensor
module
Present 0 V (2
s) and 10 V (2
s) one by one in
turn
Value of register
209 changes
from 0 to 1
QSA2700
Red flashing (0.5 s on /
0.5 s off)
Error 2, communication
error
Present 0 V (5
s) and 10 V (2
s) one by one in
turn
Value of register
209 changes
from 0 to 2
QSA2700
Red / yellow flashing (0.5
s red / 0.5 s yellow)
Warning of possible
inaccurate
measurement
Present the
measured value
Value of register
209 remains 0
without change
6.4 Disposal
The device is considered electrical and electronic equipment for disposal in terms of
the applicable European Directive and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.