Data Sheet for Product

13
Siemens
A6V11396712
Smart Infrastructure
2020-08-17
Error info
Error info
0-10 V output
Modbus
LED indication
LCD
Replace sensor
module
Present V (2 s)
and 10V (2 s)
one by one in
turn
Value of register 209
changes from 0 to 1
Red permanently on
Communication
error
Present 0V (5 s)
and 10V (5 s)
one-by-one in
turn
Value of register 209
changes from 0 to 2
Red flashing (0.5 s on/
0.5 s off)
Warning for
possible
inaccurate
measurement
Present the
measured value
Value of register 209
remains 0 without
change
Red/yellow flashing
(0.5 s red 0.5 s yellow)
Diagrams
Wiring
G, G0: Operating voltage AC 24V (SELV)/DC 13.5 to 35V
U1: Signal output DC 0 to 10V for PM2.5 with selected range in
μg/m3
U2: Signal output DC 0 to 10V for PM10 with selected range in
μg/m3
Gu: Signal ground for U1 and U2
+,-, Ref: Modbus signal
Dimensions
NOTE: Use an ARG70 adapter plate (sold seperately) to mount a QSA2700/QSA2700D
sensor on a 2 × 4 box.