Data Sheet for Product

4
Siemens
--
_c
Smart Infrastructure 2019-04-10
Enter addressing mode and configuration workflow via push button
Press the
button for
LED Action More details
1…5 s Constant red Press and hold the button
5…10 s LED off Release the button
Entering the addressing mode, LED
flashes yellow for 30 s.
Address is set to 246 temporarily.
Communication is established
automatically when:
Baud rate is 19200 (default).
Format is 1-8-E-1 (default).
Address is 246.
Then:
Master writes the Modbus
parameters.
Master writes “1” into register
4x0768 ("Bus configuration
command”) to activate the change.
After a successful pairing, the LED
flashes green for 60 s, then turns to
permanent green.
Otherwise, the LED turns back to its
original state.
LED flashes
yellow for
0…30 s
Short press the button to fix
the address to 246.
If the LED is flashing, a short press of the
push button fixes the address to 246.
The LED is off for 2 s, then turns yellow
for 2 s and then turns to permanent
green.
The address is 246.
Further configuration should be carried
out from controller side.
Reset Modbus settings or cancel resetting
Press the
button for
LED Action More details
1…5 s Constant red Press and hold the button
5…10 s LED off Press and hold the button
10…13 s Flash yellow Reset Modbus setting to
factory default if releasing the
button
1)
Release the button while the LED still
flashes yellow. LED keeps flashing yellow
for 3 s. then turns red for 1 s.
The reset is completed. LED turns to
permanent yellow.
>13 s Returns to the
initial status
Cancel resetting if releasing
the button
Release after 13 s, resetting is cancelled.
Remark:
1)
Only Modbus address, baud rate and transmission format are reset to factory default.