Installation Instructions

Installation Instructions
Document No. 129-433
February 18, 2016
QPM Series Indoor Air Quality Duct Sensors
Item Number 129-433, Rev. GA Page 1 of 4
Product Description
The QPM Series Indoor Air Quality Duct Sensors
are designed for applications where precise, stable
sensing of carbon dioxide (CO
2
), temperature, or
relative humidity sensing is required. Model
QPM2102 senses both volatile organic compounds
(VOCs) and CO
2
, with the output signal
automatically switching to reflect the higher of the
two values.
These sensors are directly wired to the controller
with 18 to 22 AWG (recommended) multi-conductor
shielded cable. The number of conductors required
depends on the model selected. All field wiring is
terminated in a terminal block on the sensor body.
The output signal is field selectabe for 0 to 10V or 0
to 5V.
Siemens CO
2
+ VOC sensors are designed to help
maximize occupant comfort and are not suitable for
use in life safety applications.
Product Numbers
Product
Number
Description
QPM2100 CO
2
sensing only
QPM2102 CO
2
and VOC sensing only
QPM2102D CO
2
and VOC sensing with display
QPM2160 CO
2
and temperature (active) sensing only
QPM2160D CO
2
and temperature (active) sensing with
display
QPM2162 CO
2
, rh and temperature (active) sensing
only
QPM2162D CO
2
, rh and temperature (active) sensing
with display
QPM2180 CO
2
and temperature (passive) sensing
only (depending on connected sensing
element-- LG-Ni1000, Pt1000, Pt100, or
NTC 10K .)
Additional Reference Documents
Technical Instructions CE1N1962
Technical Specification Sheet 149-909
Expected Installation Time
One hour
Required Tools
· Phillips screwdrivers, No. 1 and No. 2
· Wire cutters/strippers
· Medium flat-blade screwdriver
· Tape measure
· Medium-duty electric drill
· Marker or pencil
· No. 26 (0.147-inch) drill bit
· Small level
· 7/8-inch drill bit or hole saw
· Two No. 8 × 1-inch sheet metal screws
Prerequisites
· Ensure that the appropriate field wiring is
installed.
Appropriate wiring is 8 to 22 AWG
(recommended) multi-conductor shielded
cable (plenum or non-plenum as required),
within the maximum wiring run length for the
individual equipment controller. See Wiring
Diagrams to determine the required number
of conductors. The maximum recommended
length is 750 feet (229 m).
· Ensure that all wiring complies with National
Electric Code (NEC) and local regulations.
· Allow up to 96 hours for unit to reach
published accuracy.
Mounting Information
Locate the sensor:
· In the center of a duct.
· Away from fans, corners, heating and cooling
coils, and so on.
· Away from direct sunlight (for example, not
on a rooftop). To ensure correct operation,
the sensor’s ambient temperature must be
between 23°F and 133°F (–5°C to 45°C).
· Where it receives adequate airflow for
proper operation.
· Where it can be easily accessed for service.