User Manual

A6V101101338_en--_a Building Technologies
2017-03-14
Duct
air quality sensors
QPM11x4
· Maintenance-free CO
2
sensing element based on optical infrared absorption
measurement (NDIR = non dispersive infrared)
· No recalibrations required
Use
In air ducts of ventilation and air conditioning plant to enhance room comfort and to
optimize energy consumption by providing demand-controlled ventilation. The sensor
acquires CO
2
concentrations and temperature.
The sensors may not be deployed as safety devices, e.g. as gas or smoke warning
devices!
Type summary
Type Order number Designation
QPM1104 S55720-S455 Duct sensor CO
2
QPM1164 S55720-S456 Duct sensor CO
2
/T
The sensor is supplied complete with mounting flange and cable entry gland M16.
Engineering notes
The sensor must be powered by a transformer for safety extra low-voltage (SELV) with
separate windings, suited for 100 % duty.
On applications with EMC problems, use shielded cables. For secondary power lines
and signal lines, use twisted-pair cables.
Mounting notes
To ensure degree of protection IP54, the sensor must be fitted with the cable entry
pointing downward.
Important!
Cable routing and
cable selection
Mounting location and
orientation