User Manual

Siemens Building Technologies CM1N5482E / 10.1998
Landis & Staefa Division 7/8
Ambient conditions
Operation to IEC 721-3-3
Climatic conditions class 3K5
Temperature 0...50 °C
Humidity <95 % r.h.
Transport to IEC 721-3-2
Climatic conditions class 2K3
Temperature 25...+70 °C
Humidity <95 % r.h.
Mechanical conditions class 2M2
Electromagnetic compatibility
Emissions EN 50 081-1
Immunity EN 50 082-1
conformance to
EMC directive 89/336/EEC
Low voltage directive 73/23/EEC
Product standards
Switches for household and similar fixed
electrical installations EN 60 669-1
Safety class II to EN 60 730
Degree of protection IP 50 to EN 60 529
Connecting terminals (screwless) 2.5 mm
2
max.
Weight 0.173 kg
NNQ14 Q23 Q24
L
t1
t2
230 V
5482G01
max. 2 A (230 V )
min. 5 mA (5 V )
L, N Operating voltage AC 230 V
t1 HVAC switch on delay, adjustable from 0 to 300 s
(with emergency operation)
t2 HVAC switch off delay, adjustable from 0.5 to 30 min
Q14, N Control output «Lighting»
Q23, Q24 Control output «HVAC»
Control of a lighting system and a HVAC unit
U
H1
L
N
N Q14 Q23
Q24
5482A01
L
N
S
Diagrams
Connecting terminals
Connection diagram 1