Data Sheet for Product
CE1N1961en
2018-05-01
Building Technologies
1
961
QPA10… / QPA20…
QPA20…D
Room air quality sensors
QPA10
..
QPA20..
· Maintenance-free CO
2
sensing element (depending on type) based on optical
infrared absorption measurement (NDIR
1)
)
· Or with VOC
2)
sensing element based on a heated tin dioxide semiconductor
· CO
2
temperature (active or passive) and CO
2
humidity-temperature multisensor
· No recalibrations required
· Operating voltage AC 24 V or DC 15…35 V
· Signal outputs DC 0...10 V or DC 0...5 V or 4...20 mA adjustable
· Selectable passive temperature sensing element
1) NDIR = Non dispersive infrared
2) VOC = volatile organic compounds (also called mixed gas)
Use
In ventilation and air conditioning plants to enhance room comfort and optimize energy
consumption by providing demand-controlled ventilation. The sensor acquires:
· CO
2
concentrations as an indication of occupancy in rooms where smoking is
prohibited.
· VOC concentrations as an indication of odors such as tobacco smoke, body odor, or
material fumes in the room.
· Relative humidity in the room.
· Room temperature.
Sensors QPA10… and QPA20… can be used as a:
· Control sensor.
· Transmitter for building automation and control systems and / or display units
(QPA20…D only).