Installation Instructions

Installation Instructions
Document No. 129-435
February 18, 2016
QPA20xx Series Indoor Air Quality
Room Sensors
Item Number 129-435, Rev. FA Page 1 of 4
Product Description
The QPA20xx Series Indoor Air Quality Room
Sensors are designed for applications where
precise, stable sensing of carbon dioxide (CO
2
),
temperature, or relative humidity is required. The
QPA2002 models sense both volatile organic
compounds (VOCs) and CO
2
, with the output signal
automatically switching to reflect the higher of the
two values.
Siemens CO
2
+ VOC sensors are designed to help
maximize occupant comfort and are not suitable for
use in life safety applications.
Product Numbers
Product
Number
Description
QPA2000 CO
2
sensing only
QPA2002 CO
2
and VOC sensing only
QPA2002D CO
2
and VOC sensing with display
QPA2060 CO
2
and temperature sensing (active)
only
QPA2060D CO
2
and temperature (active) sensing
with display
QPA2062 CO
2
, temperature (active) and rh
sensing only
QPA2062D CO
2
, temperature (active) and rh
sensing with display
QPA2080 CO
2
and temperature (passive)
(depending on connected sensing
element *)
QPA2080D CO
2
and temperature (passive)
(depending on connected sensing
element *) with display
ARG70 Mounting Plate
(Required for installation on 2× 4
electrical box.)
* LG-Ni1000, Pt1000, Pt100, or NTC 10K ohm.
Additional Reference Documents
Technical Instructions CE1N1961
Technical Specification Sheet 149-910
Expected Installation Time
30 minutes
Required Tools
· Phillips screwdrivers, sizes 1 and 2
· Small and medium flat-blade screwdriver
· Wire cutters/strippers
· Tape measure
· Medium-duty electric drill
· Drill bit for wall anchor hole
· Marker or pencil
· Two No. 10 screws and wall anchors
Prerequisites
· Ensure that the appropriate field wiring is
installed.
Appropriate wiring is 8 to 22 AWG
(recommended) multi-conductor shielded cable
(plenum or non-plenum as required), within the
maximum wiring run length for the individual
equipment controller. See Wiring Diagrams to
determine the required number of conductors.
The maximum recommended length is 750 feet
(229 m).
· Ensure that all wiring complies with National
Electric Code (NEC) and local regulations.
· Allow up to 96 hours for unit to reach published
accuracy.
Installation
Always mount the sensor vertically.
Locate the sensor:
· According to design specifications and local
regulations.
· Where the air circulates around it freely (not in
recessed areas or behind doors).
· Allowing a minimum of 4 inches (10 cm) of free
space above and below for proper airflow and
access.