Data Sheet for Product
QPA20xx Series Indoor Air Quality Room Sensors Technical Instructions
Document Number CE1N1961
July 26, 2019
Siemens Industry, Inc. Page 7
Functional data, rh with
QPA2062 and QPA2062D
Range of use 0 to 95% rh (non-condensing)
Measuring range 0 to 100% rh
Measuring accuracy @ 73°F (23°C) and 24 Vac
0 to 95% rh + 5% rh
30 to 70% rh + 3 rh (typically)
Temperature dependency < 0.1% rh/°C
Time constant Approximately 20 seconds
Output signal, linear (terminal X2) 0 to 100% rh
Functional data,
temperature with
QPA206xx
Measuring range 32°F to 122°F (0°C to 50°C) (R2, R3)
-31°F to 95°F (-35°C to 35°C) (R1)
Measuring element NTC 10K Ω
Measuring accuracy at 24 Vac:
59°F to 95°F (15°C to 35°C) + 1.4°F (+ 0.8°C)
outside the above range, between:
-31°F to 122°F (-35°C to 50°C) + 1.8°F (+1°C)
Time constant t
63
8.5 minutes
Output signal, linear (terminal X2 or X3) 32°F to 122°F (0°C to 50°C)/
-31°F to 95°F (-35°C to 35°C)
Measured value display,
protective data
QPA2002D, QWPA2060D, QPA2062D LCD
Degree of protection, housing IP 30 to IEC 529
Safety class III to EN 60 730
Electrical connections
Screw terminals for 1 × 12 AWG or 2 × 16 AWG
Environmental
conditions
Transport:
Temperature: -13F to 158F (-25C to 70C)
Humidity: < 95% rh
Materials and colors
Cover ASA + PC, NCS S 0502-G (white)
Housing ASA + PC, NC 2801-Y43R (gray)
Mounting plate PC, NCS 2801-Y43R (gray)
Sensor (complete) Silicone-free
Packaging Corrugated cardboard
Standards
Product safety
Automatic controls for household and EN 60 730-1
similar use
Electromagnetic compatibility
Immunity (QPA2062, QPA2062D) EN 61 000-6-1
Immunity (QPA2000, QPA2002, EN 61 000-6-2
QPA2002D, QPA2060, QPA2060D)
Emissions EN 61 000-6-3
conformity EMC directive 89/336/EEC
UL conformity UL 916
conformity to Australian EM framework Radio Communication Act 1992
Radio Interference Emission Standard AS/NZS 3548
Weight (including
packaging)
Approximately 4.25 oz (0.12 kg)