Data Sheet for Product

Technical Instructions QPA20xx Series Indoor Air Quality Room Sensors
Document Number CE1N1961
July 26, 2019
Page 6 Siemens Industry, Inc.
Cable Routing and
Selection
When laying the cables, it should be considered that electrical interference increases
the longer the cables run parallel and the smaller the distance between them.
On applications with EMC problems, shielded cables should be used.
For the secondary power lines and signal lines, use cables with twisted pairs.
Mounting Notes
Inner wall of the room to be ventilated, not in niches, behind curtains, above or near
heat sources, and not exposed to direct light from spot lights.
Do not expose the sensor to direct sunlight.
Airflow of greater than 30 fpm may affect the temperature and humidity sensing
accuracy. Avoid installing in areas prone to drafts.
The end of the conduit at the sensor must be sealed to prevent inaccurate
measurements due to drafts through the conduit.
Installation Instructions are included with the unit.
Commissioning
Notes
Check the sensor’s functions can be checked 30 minutes after applying power.
Checking the CO
2
function:
In well-ventilated rooms, the sensor shows the CO
2
concentration of the outside air.
Typically, this is 360 ppm (depending on the sensor’s measuring accuracy). Also, a
basic functional check can be made by exhaling on the sensor. Note that the sensor’s
rate of response has been purposely delayed (time constant t
90
= 5 minutes).
Checking the VOC function:
Touch the sensor with a cotton ball dowsed in alcohol.
Ventilation should start when the preset switching level of the connected controller is
reached.
After applying power to sensors with display, In it will appear for about six seconds.
Specifications
Power supply
Operating voltage (SELV) 24 Vac 20%, or 15 to 35 Vdc
Frequency 50/60 Hz at 24 Vac
Power consumption 2 VA
Cable length for
measuring signal
Permissible cable length See the Technical Instructions of the
device handling the signal
Functional data, CO
2
Measuring range (MW = measured value) 0 to 2000 parts per million (ppm)
Measuring accuracy @ 73°F (23°C) < + (50 ppm + 2% measured value) *
and 1013 hPa
Temperature dependency in 41°F to 113°F + 2 ppm/°C
typically (5°C to 45°C) range
Long-time drift < + 5% measuring range/5 years
Time constant t
90
<5 minutes
Output signal, linear (terminal X1) 0 to 2000 ppm
Recalibration Not required for 8 years
*Allow up to 96 hours for unit to reach published accuracy.
Functional data,
maximum selection of
CO
2
and VOC with
QPA2002 and QPA2002D
Measuring range 0 to 2000 ppm
VOC sensitivity See Table 1
Output signal, linear (terminal X2) 0 to 2000 ppm
Response time, VOC signal t
voc
3 minutes/V