Data Sheet for Product

QPA20xx Series
Technical Instructions
Document No. CE1N1961
July 26, 2019
Indoor Air Quality Room
Sensors
Siemens Industry, Inc.
Description
The QPA20xx Series Room Air Quality Sensors are designed for applications where
precise, stable carbon dioxide or air quality sensing is required.
Several models are available with either CO
2
only, or with Volatile Organic
Compounds (VOC) (also known as mixed gas), relative humidity and/or temperature
sensing. All units deliver a voltage or current (selectable) signal and have a CO
2
measuring range of 0 to 2000 ppm.
Features
Maintenance-free, Non-Dispersive Infrared (NDIR) CO
2
sensing element is ideal for
use in spaces that are occupied 24/7.
Combination units enable a single sensor to take the place of up to three individual
sensors.
No recalibration required.
24 Vac or 15 to 35 Vdc operating voltage
0 to 10 Vdc, 0 to 5 Vdc, or 4 to 20 mA signal outputs (field selectable)
Application
For use in ventilation and air conditioning applications to enhance room comfort and to
optimize energy consumption by providing demand-controlled ventilation. The sensor
acquires:
CO
2
concentrations as an indication of occupancy in rooms where smoking is
prohibited.
The relative humidity in the room.
The room temperature.
QPA2002 models measure both CO
2
and volatile organic compounds (VOC) for
optimized indoor air quality. A single 0 to 10V, 0 to 5V, or 4 to 20 mA (selectable)
output signal is automatically adjusted to reflect the higher of the two values. This
enables the combination CO
2
+ VOC sensor to be easily substituted for a CO
2
sensor in
any demand control ventilation control system.