s 1 1601p01en 1601p01en 601 Desigo™ TRA Freely configurable flush-mounted room operator unit for KNX PL-Link QMX3.P36F QMX3.P36G • Freely configurable user interface (keys and visual items) as part of Total Room Automation • Energy efficiency function ("Green Leaf ") • Room temperature measurement • Display of room temperature, control mode, scenes etc.
Use The QMX3.P36... room operator unit is used as part of Desigo room automation to measure the room temperature as well as to operate the room functions. The room automation station determines the functions of both LCD display and keys. The room operator unit can be used together with the Desigo TRA room automation stations. Type summary, ordering Room operator units Product number Stock number Designation QMX3.P36F S55624-H100 QMX3.
Mechanical design • The unit is designed for mounting in a conduit box (A) – Square CEE/VDE (type A) – Rectangular 3 modules landscape (suitability to be clarified in advance). • The base plate (B) (rectangular or landscape) contains: – A hook to attach a securing strap to protect against tampering (the strap is not provided) – an earthing plate (quick slide connector) to connect an earthing cable • One Bezel (C) is supplied: – Siemens DELTA line (square, with the QMX3.
Engineering notes • The room operator units offer plug & play functionality. • The room operator units receive their power from the connected room automation station via the KNX PL-Link interface. • KNX PL-Link supports plug & play functionality for pre-configured devices out of the library • For KNX PL-Link wiring (topology, allowed cables and cable length), see the Desigo installation guide, CM111043. • Normally, electrical installers only install the base plate and the KNX PL-Link plug.
Mounting • The base plate contains: – A hook to attach a securing strap to protect against tampering (the strap is not provided) – An earthing plate (quick slide connector) to connect an earthing cable • The installing tube must be sealed or cold or warm air may enter the conduit box and cause faulty temperature readings by the internal sensor. • Mounting instructions are printed inside the device package and are also on the plastic bag.
Installation • For KNX PL-Link wiring (topology, allowed cables and cable length), see the Desigo TRA installation guide, CM111043. • Use the correct cables for the KNX PL-Link bus • Do not interchange the wires of the KNX PL-Link cable. – The red terminal is for KNX PL-Link + – The gray terminal is for KNX PL-Link – • Observe all local installation regulations.
Diagnostics Reset to factory setting Press "Conn. Test" to test the KNX PL-Link connection. A popup window shows the progress of the connection test: STOP Note! This operation resets all user preference data and configuration settings to factory default. This operation is irreversible. Press "Fact. Reset". The device is locked and reboots within 10 seconds. The room automation station deletes it from its device list. During this time, it is safe to remove the device from the network.
Step 3 Function Normal operation Description After startup, the device goes to normal operation (example view; picture depends on application in room automation station). 4 Configuration required When configuration is faulty, the default page "Initial Menu" is displayed: temperature that is measured by the local temperature sensor along with a menu for network commissioning and diagnostics.
Single-page display With a single-page page set, information is usually is laid out in the following format: Line 1 Line 2 Line 3 Line 4 Title / read-only data point information Operable data point information Temperature, air quality, fan speed, etc.
Status information A list item provides status information: • Tick: Indicates the current selection from the room automation station. A change from hourglass to tick indicates that the automation station has confirmed the modifications the user just made. • Hourglass: Indicates the progress of the selected activity. • Lock: Indicates locked entries that cannot be selected / enabled. • Floppy disk: Is only used in scene saving, and will be displayed for 1 second, then go back to "Tick".
Ambient conditions IEC 721 Environmental conditions Temperature Humidity Mechanical conditions Standards and directives EU conformity (CE) compliance compliance CSA compliance Normal operation Class 3K5? 0...50 °C < 85 % rh Class 3M2 CM2T1601xx UL916 Transport Class 2K3? – 25...70 °C < 95 % rh Class 2M2 *) Part 15 of the FCC rules C22.2 No 205 – Signal equipment C22.
Connection R1 QMX3... room operator unit N1 Controller, actuator = – + – + + – KNX / PL-Link plug STOP Note! Twisted pair + – Red Gray KNX PL-Link (positive) KNX PL-Link (negative) Wires are NOT interchangeable! The device is protected against faulty wiring, but communications does not work on interchanged wires. 1601A03 Tool plug (2.5 mm Jack) + _ RJ45 plug of the tool cable 8 1601A02 1 1 2 3 4 CE+, KNX CE–, KNX N.C. N.C. 5 6 7 8 Voltage 16 V N.C.
Dimensions Operator unit Bezel DELTA line (square) Base plate square Bezel similar to DELTA azio (rectangular) Base plate rectangular 13 / 14 Siemens Building Technologies QMX3...
/ 14 2016 Siemens Switzerland Ltd Subject to change Siemens Building Technologies QMX3...