Basic Documentation

Table Of Contents
46 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_07
Smart Infrastructure ACS engineering 2020-06-20
6.3 ACS Parameter description
Factory settings are boldfaced.
6.3.1 Communication
Designation Values Description
Geographical zone (apartment) ---, 1...126 Geographical zone, apartment or room group
Geographical zone (room) ---, 1…63 Geographical zone, room
Geographical zone (subzone) ---, 1…15 Geographical zone, subzone
6.3.2 Universal temperature sensor
Designation Values Description
LTE transmission zone ---, 1…4095 Sending zone for KNX/ACS
Sensor correction -5...+5K
in 0.1K steps
0K
Correction of universal temperature sensor value
6.3.3 Room humidity sensor
Designation Values Description
LTE transmission zone ---, 1…4095 Sending zone for KNX/ACS
6.3.4 Room air quality sensor
Designation Values Description
LTE transmission zone ---, 1…4095 Sending zone for KNX/ACS
Altitude above sea level [m] 0…3000 m
0 m
Entry of altitude above sea level at measuring location to correct CO
2
measured
value