Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_07
Smart Infrastructure ETS engineering 2020-06-20
Designation Values Type
Visible parameter name in ETS Range
(Default)
Unit
QMX3.P30
QMX
3.P40
QMX3.P7
0
QMX3.P34
QMX3.P
44
QMX3.P74
QMX3.P37
QMX3.P02
5.5.3 Room relative humidity sensor
Humidity: Send following change by 2; 3; 4; 5; 7; 10 (2%) %r.h. X X X X X
Humidity: Send cyclically after 1; 2…45; 60 (15 min) min X X X X X
5.5.4 Room relative humidity control
To display this section, enable the option “Activate room humidity control” in Device
Default switching point stage 1 (%r.h.) 0…100 (40) %r.h. X X X X X X X X
Default switching point stage 2 (%r.h.) 0…100 (70) %r.h. X X X X X X X X
Default switching point stage 3 (%r.h.) 0…100 (90) %r.h. X X X X X X X X
Hysteresis 2;3;4;5;7;10 (5%) %r.h. X X X X X X X X
If room humidity exceeds a switching point r.h., the control value r.h.
for the respective stage is switched on.
Control value r.h. is switched off again when room humidity
< switching point r.h. – hysteresis.
Control value stage 0 (%) 0…100 (0) % X X X X X X X X
Control value stage 1 (%) (>stage 0) 0…100 (35) % X X X X X X X X
Control value stage 2 (%) (>stage 1) 0…100 (70) % X X X X X X X X
Control value stage 3 (%) (>stage 2) 0…100 (100) % X X X X X X X X
If room humidity exceeds switching point r.h., the control value
parameterized for this stage is issued.
The control value again issues the next lower stage value when room
humidity < switching point r.h. – hysteresis.
Stage when overridden 0;1;2;3 (3) X X X X X X X X
Send cyclically after
Do not send cyclically
1;2;3...30;45;60 (15 min)
min. X X X X X X X X