Basic Documentation
Table Of Contents
- Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
- Contents
- 0 About this document
- 1 Devices
- 2 Safety and EMC optimization
- 3 Mounting and electrical installation
- 4 Functionality / Use
- 5 ETS engineering
- 5.1 Engineering
- 5.2 Commissioning
- 5.3 Communication objects
- 5.4 Room operator unit visualization and operation
- 5.5 ETS parameter description
- 5.5.1 Room temperature sensor
- 5.5.2 Room temperature control
- 5.5.3 Room relative humidity sensor
- 5.5.4 Room relative humidity control
- 5.5.5 Room air quality sensor
- 5.5.6 Room air quality control
- 5.5.7 Device display parameters
- 5.5.8 HVAC operation and display
- 5.5.9 Operation and display: Relative humidity visualization
- 5.5.10 Display on QMX3.P70 Air quality indication LED
- 5.5.11 Operation and display: air quality
- 5.5.12 Operation of light, shading and scenes
- 5.6 Examples for the operation of touch keys and display elements
- 6 ACS engineering
36 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_07
Smart Infrastructure ETS engineering 2020-06-20
*)
PID parameter set for the heating sequence
Heating type Xp TiN TiV Nz SD
Radiator heating slow 2 K 5400s 450s 0,1K 0.8K
Radiator heating fast 2 K 3600s 540s 0,1K 0.8K
Floor heating slow 2 K 7200s 540s 0,1K 0.8K
Floor heating fast 2 K 5400s 540s 0,1K 0.8K
PID parameter set for the cooling sequence
Cooling type Xp TiN TiV Nz SD
Chilled ceiling 2 K 5400s 450s 0,1K 0.8K
Floor cooling 2 K 5400s 540s 0,1K 0.8K
Regardless of the setting of the control signal type "PWM" or "continuous", all 4
objects are switched on. The option "Do not send cyclically" is not operable for the
moment.
Note