PID parameter set for the heating sequence
Heating type Xp TiN TiV Nz SD
Radiator heating slow 2 K 5400s 450s 0,1K 0.8K
Radiator heating fast 2 K 3600s 540s 0,1K 0.8K
Floor heating slow 2 K 7200s 540s 0,1K 0.8K
Floor heating fast 2 K 5400s 540s 0,1K 0.8K
PID parameter set for the cooling sequence
Cooling type Xp TiN TiV Nz SD
Chilled ceiling 2 K 5400s 450s 0,1K 0.8K
Floor cooling 2 K 5400s 540s 0,1K 0.8K
Regardless of the setting of the control signal type "PWM" or "continuous", all 4
objects are switched on. The option "Do not send cyclically" is not operable for the
moment.