Basic Documentation
Table Of Contents
- Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
- Contents
- 0 About this document
- 1 Devices
- 2 Safety and EMC optimization
- 3 Mounting and electrical installation
- 4 Functionality / Use
- 5 ETS engineering
- 5.1 Engineering
- 5.2 Commissioning
- 5.3 Communication objects
- 5.4 Room operator unit visualization and operation
- 5.5 ETS parameter description
- 5.5.1 Room temperature sensor
- 5.5.2 Room temperature control
- 5.5.3 Room relative humidity sensor
- 5.5.4 Room relative humidity control
- 5.5.5 Room air quality sensor
- 5.5.6 Room air quality control
- 5.5.7 Device display parameters
- 5.5.8 HVAC operation and display
- 5.5.9 Operation and display: Relative humidity visualization
- 5.5.10 Display on QMX3.P70 Air quality indication LED
- 5.5.11 Operation and display: air quality
- 5.5.12 Operation of light, shading and scenes
- 5.6 Examples for the operation of touch keys and display elements
- 6 ACS engineering
28 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_07
Smart Infrastructure ETS engineering 2020-06-20
Obj. Object name Function Type / Length Flags
QMX3.P30
QMX3.P40
QMX3.P70
QMX3.P34
QMX3.P44
QMX3.P74
QMX3.P02
QMX3.P37
Room humidity sensor
25 Room relative hum idity [%] relative room hum idity in %
9.007
2 bytes
CRWU
X X X X
Room humidity control
26 Switching point r.h. - stage 1 relative hum idity in %
9.007
2 bytes
CRWU
X X X X X X X X
27 Switching point r.h. - stage 2 relative hum idity in %
9.007
2 bytes
CRWU
X X X X X X X X
28 Switching point r.h. - stage 3 relative hum idity in %
9.007
2 bytes
CRWU
X X X X X X X X
29 Control value r.h. cont. - manual setp. Setpoint in 0 to 100%
5.001
1 byte
CRWU
X X X X X X X X
30 Control value r.h. cont. - manual mode Manual/Auto mode
1.003
1 bit
CRWU
X X X X X X X X
31 Enable room r.h. controller On/Off
1.003
1 bit
CRWU
X X X X X X X X
32 Override room r.h. controller Ventilation (Boost) on/off
1.003
1 bit
CRWU
X X X X X X X X
33 Control value r.h. stage 1 - on/off 1 = On / 0 = Off
1.001
1 bit
CRT
X X X X X X X X
34 Control value r.h. stage 2 - on/off 2 = On/0 = Off
1.001
1 bit
CRT
X X X X X X X X
35 Control value r.h. stage 3 - on/off 3 = On/0 = Off
1.001
1 bit
CRT
X X X X X X X X
36 Control value r.h. - cont 0 - 100%
5.001
1 byte
CRT
X X X X X X X X
Provides the room hum idity value from the integrated sens or.
Units with display: Must be placed in a group addres s to display operation/symbol on the display.
External room hum idity sensor values, see object 70
External outside humidity sensor values, see object 69
The configured default switching points apply as long as no value is received from the bus.
In manual mode (obj. 30, 1=Manual), a setpoint is received via this object and outputted directly as modulating positioning
signal (object 36).
Changing over to the manual mode permits receipt of a manual setpoint (Obj. 29) for the modulating positioning signal
(Obj. 36). Otherwise, the configured positioning signals for the applicable stage are outputted.
All controller outputs are switched off upon receipt of "Controller off".
The controller remains disabled until "Controller on" is received. The default value is controller on = 1.
For controller override, the stage defined in the parameter "Stage is overridden" is enabled. Objects 33, 34, 35 as sume
only the value "1=On" for the corresponding object; the other two objects the value "0 = Off". The modulating positioning
signal (obj. 36) outputs the value configured for the applicable stage.
Override has the highest priority. The default state is "Normal".
The stage belonging to positioning signal r.h. is switched on if room humidity overrides a
switching point r.h. The pos itioning signal r.h. is switched off again for room humidity <
switching r.h. - hysteresis.
The positioning signal configured for the stage is outputted if room humidity overrides a
switching point r.h. The pos itioning signal once again outputs the value of the next smaller
stage, for room humidity < switching r.h. - Hysteresis.
Devices