Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_07
Smart Infrastructure ETS engineering 2020-06-20
Obj. Object name Function Type / Length Flags
QMX3.P30
QMX3.P40
QMX3.P70
QMX3.P34
QMX3.P44
QMX3.P74
QMX3.P02
QMX3.P37
Room temperature setpoint, operating modes, window state, occupancy
10 Room tem perature: Setpoint abs olute [°C]
9.001
2 bytes
CRWU
X X X X
11 Room tem perature: Setpoint relative [K]
9.002
2 bytes
CWU
X X X X
12 Room tem perature: Setpoints heating
222.100
6 bytes
CRWU
X X X X X X X X
13 Room tem perature: Setpoints cooling
222.100
6 bytes
CRWU
X X X X X X X X
14 Room operating mode: Time switch
1= Comfort, 2 = Precomfort,
3 = Eco, 4 = Protection
20.102
1 byte
CRWU
X X X X X X X X
15 Room operating mode: Preselection
0 = Auto, 1= Comfort, 2 = Precomfort,
3 = Eco, 4 = Protection
20.102
1 byte
CRWU
X X X X
16 Room operating mode: State
1= Comfort, 2 = Precomfort,
3 = Eco, 4 = Protection
20.102
1 byte
CRT
X X X X X X X X
17 Comfort mode: Timer button Activate comfort extension
1.017
1 bit CW
X X X X X X X X
X X X X X X X X
18 State window 1 (1=open / 0=close) 1 = Open / 0 = Closed
1.019
1 bit
CRWU
X X X X X X X X
19 State window 2 (1=open / 0=close) 1 = Open / 0 = Closed
1.019
1 bit
CRWU
X X X X X X X X
20 State window 3 (1=open / 0=close) 1 = Open / 0 = Closed
1.019
1 bit
CRWU
X X X X X X X X
21 State window 4 (1=open / 0=close) 1 = Open / 0 = Closed
1.019
1 bit
CRWU
X X X X X X X X
X X X X X X X X
22 Presence state 0 = non-occupancy / 1 = occupancy
1.018
1 bit
CRWU
X X X X X X X X
23 Room tem perature: Setpoint Heating [°C]
9.001
2 bytes
CRT
X X X X X X X X
24 Room tem perature: Setpoint Cooling [°C]
9.001
2 bytes
CRT
X X X X X X X X
160 Room tem perature: Econom y heating setpoint Temperature (°C)
9.001
2 bytes
CWU
X X X X X X X X
161 Room tem perature: Precomfort heating setpoint Temperature (°C)
9.001
2 bytes
CWU
X X X X X X X X
162 Room tem perature: Com fort heating setpoint Temperature (°C)
9.001
2 bytes
CWU
X X X X X X X X
163 Room tem perature: Com fort cooling setpoint Temperature (°C)
9.001
2 bytes
CWU
X X X X X X X X
164 Room tem perature: Precomfort cooling setpoint Temperature (°C)
9.001
2 bytes
CWU
X X X X X X X X
165 Room tem perature: Econom y cooling setpoint Temperature (°C)
9.001
2 bytes
CWU
X X X X X X X X
The extension time can be configured.
Units with dis play: Mus t be placed in a group addres s to dis play operation/symbol on the dis play.
These objects available only when PID control is enabled.
Units with dis play: Objects must be placed in a group address to display open window symbol on the display.
(corres ponds to object 55 for units with display)
(corres ponds to object 56 for units with display)
This is a setpoint set. It can be used to adjust all heating setpoints (Com fort, Precomfort and Eco)
This is a setpoint set. It can be used to adjust all cooling setpoints (Comfort, Precom fort and Eco)
The controller operating mode must be set to Auto to receive operating modes from a time switch over the bus. The
operating mode Auto remains until overwritten by another object (15 or 58).
Room operating mode is received over the bus.
(corres ponds to object 58 for units with display)
Room operating mode is provided to the bus.
Devices
Receives the occupancy state over the bus, e.g. from a presence detector.
The active heating setpoint can be read over the bus with object 23.
Note: The Precomfort setpoint is adjusted if the com fort setpoint, visible on the display (vis ible setpoint -3 K), is adjusted
below the Precomfort setpoint. The internal setpoints (Heating Comfort, Heating Precomfort, Heating Eco) can be adjusted
via bus using objects 160, 161 and 162, or using object set 12
The active cooling setpoint can be read over the bus with object 24.
Note: The Precomfort setpoint is adjusted if the com fort setpoint, visible on the display (vis ible setpoint +3 K), is adjusted
above the Precomfort setpoint. The internal setpoints (Cooling Comfort, Cooling Precomfort, Cooling Eco) can be adjusted
via bus using objects 163, 164 and 165, or using object set 13
The initial Economy heating setpoint is adjus ted via bus using this object.
These objects (160...165) mus t be activated in ETS:
Room tem perature control --> "Room temperature setpoints as com munication objects"
The initial Precomfort heating setpoint is adjus ted via bus using this object. See als o object 160.
The initial Comfort heating setpoint is adjus ted via bus using this object.
See also object 160.
The initial Comfort cooling setpoint is adjus ted via bus using this object.
See also object 160.
The initial Precomfort cooling setpoint is adjusted via bus using this object. See also object 160.
The initial Economy cooling setpoint is adjusted via bus using this object.
See also ob ject 160.