Basic Documentation
Table Of Contents
- Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
- Contents
- 0 About this document
- 1 Devices
- 2 Safety and EMC optimization
- 3 Mounting and electrical installation
- 4 Functionality / Use
- 5 ETS engineering
- 5.1 Engineering
- 5.2 Commissioning
- 5.3 Communication objects
- 5.4 Room operator unit visualization and operation
- 5.5 ETS parameter description
- 5.5.1 Room temperature sensor
- 5.5.2 Room temperature control
- 5.5.3 Room relative humidity sensor
- 5.5.4 Room relative humidity control
- 5.5.5 Room air quality sensor
- 5.5.6 Room air quality control
- 5.5.7 Device display parameters
- 5.5.8 HVAC operation and display
- 5.5.9 Operation and display: Relative humidity visualization
- 5.5.10 Display on QMX3.P70 Air quality indication LED
- 5.5.11 Operation and display: air quality
- 5.5.12 Operation of light, shading and scenes
- 5.6 Examples for the operation of touch keys and display elements
- 6 ACS engineering
19 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_07
Smart Infrastructure Functionality / Use 2020-06-20
The digits "0xxx" and "00xx" are displayed on power-up:
0xxx is the FW version
00xx is the Build version
4.4 Functions
The room operator units with control functions can be integrated in a KNX network.
The control functions for room temperature and ventilation allow for immediate
control of suitable actuators to control heating, cooling, and ventilation.
4.4.1 Measuring
The room operator units measure the room temperature via an integrated sensing
element. The room temperature can be transmitted to other bus members and
serves in KNX as control variable of the integrated room temperature controller.
The outdoor temperature received via the KNX bus is only used for indication on
the display and has no effect on the control.
The room operator units acquire the relative humidity in the room with the aid of a
humidity sensing element integrated in the front module. The relative room
humidity can be transmitted to other bus members and serves in KNX as control
variable of the integrated ventilation controller.
The room operator units determine the CO
2
concentration via infrared absorption
measurement (NDIR). The sensor provides exact measurements at all times and
does not require maintenance or recalibration thanks to an integrated, stable
reference light source. The CO
2
concentration can be transmitted to other bus
members and serves in KNX as control variable of the integrated ventilation
controller.
The background-lit symbol informs on the current level of CO
2
in the room. The
colors green / orange / red of the background lighting indicate good / moderte /
poor air quality. The display can be switched on or off by another bus member, e.g.
switch or timer.
Temperature
(All Types)
Relative humidity
(QMX3.P70, QMX3.P74)
CO
2
concentration
(QMX3.P70, QMX3.P74)
Air quality indication
(QMX3.P70)