Basic Documentation
Table Of Contents
- Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
- Contents
- 0 About this document
- 1 Devices
- 2 Safety and EMC optimization
- 3 Mounting and electrical installation
- 4 Functionality / Use
- 5 ETS engineering
- 5.1 Engineering
- 5.2 Commissioning
- 5.3 Communication objects
- 5.4 Room operator unit visualization and operation
- 5.5 ETS parameter description
- 5.5.1 Room temperature sensor
- 5.5.2 Room temperature control
- 5.5.3 Room relative humidity sensor
- 5.5.4 Room relative humidity control
- 5.5.5 Room air quality sensor
- 5.5.6 Room air quality control
- 5.5.7 Device display parameters
- 5.5.8 HVAC operation and display
- 5.5.9 Operation and display: Relative humidity visualization
- 5.5.10 Display on QMX3.P70 Air quality indication LED
- 5.5.11 Operation and display: air quality
- 5.5.12 Operation of light, shading and scenes
- 5.6 Examples for the operation of touch keys and display elements
- 6 ACS engineering
17 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_07
Smart Infrastructure Functionality / Use 2020-06-20
4.2 Use
Six complementary device types are available which can control HVAC and electric
applications.
· Room temperature, humidity, and CO
2
content of the room are controlled
according to the demand and to energy efficiency criteria.
· Four freely parameterizable pairs of touchkeys can be configured for light
switching, dimming, blinds, scenes, sending values, etc.
The sensors in the room operator unit measure:
– Room temperature.
– Relative room humidity.
– CO
2
concentration in rooms with varying occupancy due to time or number of
people such as in museums, movie theaters, offices, meeting rooms, class
rooms, auditoriums, hospitals, living spaces.
The room operator units control and operate:
– Room temperature (via PID controller)
– Humidity (via threshold value)
– Air quality (via threshold value)
– Fan stages (independent of temperature, air quality and humidity control
functions)
– Room operating modes
– Input of the occupancy state
as well as
– Switching of electrical equipment
– Switching and dimming of lights
– Control of shading / blinds
– Selecting and saving of scenes
The room operator units with display show the following information about the
room:
– Present room temperature, outdoor temperature.
– Present room humidity, outdoor humidity .
– Present room air quality .
– State of window contacts
– Device mode (e.g. heating, cooling).
Details