User Manual
45 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_06
Building Technologies ACS engineering 2019-04-08
Variant 2
1. Set addressing mode for the room operator unit (briefly press button on
device LED is red).
2. In the ACS790 device list, use "Addressing mode…" to select the
currently active device Enter a physical address in the "Address
assignment" dialog Click "Write".
Enter a physical address and short description for the selected room
operator
unit
.
Close the "
Address assignment“ dialog by clicking "Write…“.
Repeat these steps f
or all room operator units to be commissioned.
Then: Continue
parameterization in ACS790.
The sensor can be operated in both communication modes at the same time.
To do this, commissioning with both ACS and ETS is required.
Only the sensor values (T, R.F., CO
2
) of the QMX3... devices can be used with
Synco ACS.
To activate them set the zones accordingly in ACS.
ACS settings and ETS settings do not influence each other.
Commissioning with
ACS and ETS