User Manual

Siemens Building Technologies CM1N1513E / 02.1999
Landis & Staefa Division 3/4
The hygrostat should be mounted on an inner wall approximately 1.5 m above the floor
and at least 0.5 m from the next wall.
At the location where the unit is mounted, there should be a natural circulation of room
air (no draughts, no corners of the room, not behind curtains, not too close to doors and
windows, and not on an outer wall). Sources of heat and refrigeration (radiators, com-
puters, TV sets, concealed heating pipes, hot or cold water pipes) must be in an ade-
quate distance.
The hygrostat should not be exposed to direct solar radiation.
The unit is supplied with mounting instructions.
Setpoint range 30…100 % r.h.
Control mode on/off
Switching differential approx. 4 % r.h. (fixed)
Type of switch potential-free microswitch (S.P.D.T.)
Contact rating
Humidification
Maximum 5 (0.2) A, AC 250 V
Minimum 100 mA, AC 24 V
Dehumidification
Maximum 3 (0.2) A, AC 250 V
Minimum 100 mA, AC 24 V
Perm. ambient temperature
Operation 10…60 °C
Storage 20…+70 °C
Degree of protection IP 30 to EN 60 529
Safety class II to EN 60 730
conformity to low voltage directive 73/23/EEC
Radio interference protection to DIN 55 014
Connection terminals for 0.5 mm dia. min.
2 x 1.5 mm
2
max.
Materials
Sensing element plastic texture
Casing plastic (ABS)
Weight approx. 0.06 kg
Mounting notes
Mounting location
Mounting instructions
Technical data